4.4 Commissioning and startup wizard
4.4.1 Commissioning steps:
4.4.2 Startup wizard
Vacon 10 runs the startup wizard in first power-up. After that the wizard can be run
by pressing STOP for 5 seconds in main menu. The following figures show the pro-
cedure.
NOTE! Running the startup wizard will always return all parameter
settings to their factory defaults!
Figure 8: Vacon 10 startup wizard (General purpose application)
1. Read safety instructions on page 1
7. Perform test run without motor, see the
User Manual at www.vacon.com
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without motor being con-
nected to the process
3. Check quality and quantity of cooling air
9. Perform an identification run (Par. ID631)
4. Check that all start/stop switches are in
STOP position
10. Connect the motor to the process and per-
form test run once again
5. Connect the drive to mains
11. Vacon 10 is now ready for use
6. Run the Startup wizard and set all necessary
parameters
Table 2: Commissioning steps
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
FAULT
ALARM
STOP
READY RUN
REF
MON
PAR
FLT
rp m
Push to enter edit mode
Select motor
nominal speed
and push
to confirm.
Press STOP
for 5 seconds
in main menu
1
4
3
PERFORM THE SAME
PROCEDURE FOR PAR. 1.4,
MOTOR NOMINAL CURRENT
5
PERFORM DRIVE SETUP,
PAR. 13.2, SEE NEXT PAGE
2
Alternates
in the display