Vacon 10 Quick Manual - page 6
5
•
vacon
control i/o
Tel. +1 877 822 6606 • Fax +1 717 264 3115
3
3. CONTROL I/O AND TERMINALS(API FULL)
Reference:
Potentiometer: 1~10K +/- 5%
Table 1: Vacon 10 General purpose application default I/O
configuration and connections ,API Full(see information on other API’s
in User manual)
P) = Programmable function, see User manual, Parameters
Vacon 10 I/O terminals:
Terminal
Signal
Factory preset
Description
1
+10Vref
Ref. voltage out
Maximum load 10 mA
2
AI1
Analog signal in 1
Freq. reference
P)
0 - +10 V Ri = 200 k
(min)
3
GND
I/O signal ground
6
24Vout
24V output for DI's
%, max. load 50 mA
7
GND
I/O signal ground
8
DI1
Digital input 1
Start forward
P)
0 - +30 V Ri = 12 k
min
9
DI2
Digital input 2
Start reverse
P)
10
DI3
Digital input 3
Preset speed B0
P)
A
A
RS485 signal A
FB Communication
Positive
B
B
RS485 signal B
FB Communication
Negative
4
AI2
Analog signal in 2
PI actual value
P)
0(4) - 20 mA, Ri = 200
5
GND
I/O signal ground
13
GND
I/O signal ground
14
DI4
Digital input 4
Preset speed B1
P)
0 - +30 V Ri = 12 k
min
15
DI5
Digital input 5
Fault reset
P)
16
DI6
Digital input 6
Disable PI control
P)
18
AO
Analog signal out
Output frequency
P)
0(4) - 20 mA, RL = 500
20
DO
Digital signal out
Active = READY
P)
Open collector, max. load
48V/50mA
22
RO 13
Relay out 1 Active = RUN
P)
Max. switching load:
250Vac/2A or 250Vdc/0,4A
23
RO 14
24
RO 22
Relay out 2 Active = FAULT
P)
Max. switching load:
250Vac/2A or 250Vdc/0,4A
25
RO 21
26
RO 24
Ω
20
±
Ω
Ω
Ω
Ω
mA
4
5
13 14 15
16 18 20
1
9
8
7
6
3
2
10
A I2 GND GND DI4 DI5 DI6 AO DO
+10V A I1 GND
GND
24V
DI1 DI2 DI3
RO1 RO1
22 23
A
B
RO2
-
RO2
RO2
26
25 24
+
= API LIMITED
= API RS485