4 Connecting to power supply
VEGAPULS 61 • 4 … 20 mA/HART - four-wire
47100-EN-180226
4 Connecting to power supply
4.1 Connecting
The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.
Connection to the display and adjustment module or to the interface
adapter is carried out via contact pins in the housing.
Information:
The terminal block is pluggable and can be removed from the
electronics. To do this, lift the terminal block with a small screwdriver
and pull it out. When reinserting the terminal block, you should hear it
snap in.
Proceed as follows:
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Removeapprox.10cm(4in)ofthecablemantle(signaloutput),
stripapprox.1cm(0.4in)insulationfromtheendsoftheindi-
vidual wires
4. Insert the cable into the sensor through the cable entry
Fig. 6: Connection steps 5 and 6
5. Insert the wire ends into the terminals according to the wiring plan
Information:
Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-
eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithout
end sleeves, press the terminal from above with a small screwdriver,
the terminal opening is then free. When the screwdriver is released,
the terminal closes again.
Connection technology
Connection procedure