5 Set up with the display and adjustment module
VEGAPULS 61 • 4 … 20 mA/HART - four-wire
47100-EN-180226
3. Select in the menu item "Application" the vessel, the application
andthevesselform,forexample,storagetank.
4. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
100%
0%
0,5 m (19.68
")
5 m
(196.9
")
2
1
3
Fig. 10: Parameterisation example, Min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
otherdistances,forexample,10%and90%isalsopossible.Starting
pointforthesedistancespecificationsisalwaysthesealsurfaceof
thethreadorflange.
The function "Echo curve memory" makes it possible to save the
echo curve at the time of setup. This is generally recommended, and
Parameterization example
Diagnostics - Echo curve
memory