Vega VEGAPULS 61 Quick setup manual - Module
14
5 Set up with the display and adjustment module
VEGAPULS 61 • 4 … 20 mA/HART - four-wire
47100-EN-180226
5 Set up with the display and adjustment
module
5.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-
ent positions - each displaced by 90°. It is not necessary to interrupt
the power supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module on the electronics in the
desired position and turn it to the right until it snaps in.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.
Fig. 9: Installing the display and adjustment module in the double chamber
housing
Note:
Ifyouintendtoretrofittheinstrumentwithadisplayandadjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.
5.2 Parameter adjustment
1. Go to the menu "Setup" via the display and adjustment module.
2. In the menu item "Medium"you select the medium of your applica-
tion,forexample"Aqueous solution".
Set parameters