WEG PLC300 User Manual - page 37
Configuration of the PLC300
PLC300 | 7-7
In the editing of the TCP port, in addition to the upward and downward keys, the number
can be typed directly by the numeric keyboard. The key returns to the initial value,
with no change.
In the editing of the authentication of the IP address, the number can be typed directly by
the numeric keyboard. The key deletes the last digit.
IP Authentication: 4 address bytes that identify the only remote IP address that can connect
to the PLC300. All the fields in zero disable the IP authentication and any remote address
can connect to PLC300.
7.13 SD CARD – BACKUP HMI VERSION
It allows to record (PLC300 -> SD card) or upload (SD card -> PLC300) a resource, setup
configurations and firmware in the SD card connected to the PLC300.
For protection of the user’s data, a protection password for the SD card can be programmed
in the WPS. In this case, a screen to enter a password of up to eight digits will be displayed.
In order to access the functions of backup and data restoration, the password must be
entered correctly.
S D C a r d - B a c k u p
- - - - - - - - - - - - - - - - - - - -
U n l o c k P a s s w o r d :
The memory card must be of the SD type with FAT32 formatting. The faster the card (class
of the card), the shorter the recording time. This is important in case of regular variable
log recordings, for instance.
The arrows and select the option to be performed.
S D C a r d - B a c k u p
- - - - - - - - - - - - - - - - - - - -
> E q u i p . N u m . :
S a v e R e s o u r c e
L o a d R e s o u r c e
S a v e S e t u p
L o a d S e t u p
S a v e F i r m w a r e
L o a d F i r m w a r e
S a v e Fu l l B a c k u p
L o a d Fu l l B a c k u p
The ‘Equip. Num.:’ or number of the equipment indicates the folder where the files of the
selected function will be recorded or from where they will be uploaded. It may vary from
0001 to 9999.