WEG PLC300 User Manual - page 41
Configuration of the PLC300
PLC300 | 7-11
The new password must be confirmed on the next line.
C h a n g e S E T U P P a s s w d
- - - - - - - - - - - - - - - - - - - -
N e w p a s s w o r d : * * * *
R e t y p e
: * * * *
If there is a typo and the confirmation fails, the new password is requested again, until it
is confirmed or
If there is a confirmation of the new password, the message is shown:
PASSWORD REDEFINED.
Indicating success in the operation. In this case, the screen to change the password is
abandoned, returning to the main menu of the setup.
The arrow or keys work as backspace.
7.16 WATCHDOG
It allows configuring the watchdog of the PLC300.
W a t c h d o g
- - - - - - - - - - - - - - - - - - - -
> T i m e W D : 0 0 5 0 0 m s
R e s e t P L C : N o
W D O u t p u t : N o n e
O u t p u t S t : T u r n o f f
The arrows and select the option to be changed. By pressing
cursor flashes in the operating mode to be changed.
The arrows and browse through the possible values:
WD Time: allows configuring the watchdog overflow time from 300 ms to 99999 ms.
Reset PLC: defines whether the occurrence of WD will reset the PLC and run the
application again, or it will go to a safe state, configured in the following options.
WD Output: allows choosing an output of exclusive use for the WD, which can be DO8
or DO9. The writing on it via Ladder will have no effect; it will remain in high level until the
occurrence of the watchdog.
Output St.: allows configuring whether the other outputs will keep the state or will turn
of in the occurrence of the WD.