WEG SCA06 User Manual - page 24
3
Installation and Connection
3-6 | SCA06
Figure 3.3: Side by side mounting without side clearance
3.2 ELECTRICAL INSTALLATION
DANGER!
The following information is merely a guide for proper installation. Comply with applicable local
regulations for electrical installations.
DANGER!
Les informations suivantes constituent uniquement un guide pour une installation correcte. Respectez
les réglementations locales en vigueur pour les installations électriques.
DANGER!
Make sure the AC power supply is disconnected before starting the installation.
DANGER!
Vérifiez que l'alimentation secteur CA est débranchée avant de commencer l'installation.
3.2.1 Identification of the Power Terminals and Grounding Points
NOTE!
The model SCA06B05P0D2 can operate normally with three phases or with two phases (single-phase
supply) with a derating from 5 A to 4 A of the rated output current. The AC supply voltage, in this
case, may be connected to two of any input terminals (L1, L2 or L3). Whenever the SCA06B05P0D2
operates with single-phase supply, the P00217 parameter must be reprogrammed.