WEG SCA06 User Manual - page 38
3
Installation and Connection
3-20 | SCA06
NOTE
At the end of the useful life, do not dispose of the battery in common garbage, but in a proper place
for batteries.
3.2.4.3 Control Inputs and Outputs (X1)
The control connections (analog inputs/outputs, digital inputs/outputs) must be done to connector X1 of the SCA06.
The typical connection functions are shown in
Figure 3.12 on page 3-20
.
X1
Description
Function
Specification
1
C
Digital output 1
relay
Vmax: 240 Vac
200 Vdc
Imax.: 0.25 A @ 240 Vac
0.50 A @ 125 Vac
2.00 A @ 30 Vdc
Typical ton/off : 3 ms
Average useful life: 100,000 operations.
2
NA
3
DI1
Digital input 1
opto-coupled
Digital input 2
opto-coupled
High level: ≥ 18 V
Low level: ≤ 3 V Max voltage: 30 V
Input current: 3.7 mA@24 Vdc
Maximum frequency: 500 kHz
Maximum delay time: 0.5 us
4
DI2
5
COM 1,2
6
DI3
Digital input 3
opto-coupled
High level: ≥ 18 V
Low level: ≤ 3 V Max voltage: 30 V
Input current: 11 mA @ 24 Vdc
Maximum delay time: 100 us
7
COM 3
8
AI1 +
Analog input 1
differential
Signal: -10 a +10 V
Resolution: 12 bits
Vmax: ±14 V
Impedance: 400 kΩ
9
AI1 -
Figure 3.12: Connector X1
For the correct installation of the control wiring, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring in X1 with shielded cable and separated from the other wiring (power, control in 110 / 220 Vac, etc.),
according to
Table 3.4 on page 3-21
. In case the crossing of those cables is unavoidable, it must be done in
a perpendicular way, keeping the minimum distance of 5 cm (1.96 in) in this point.
4. Relays, contactors, solenoids or coils of electromechanical brakes installed close to servo drives may occasionally
generate interference in the control circuitry. In order to eliminate this effect, RC suppressors (with AC power
supply) or freewheel diodes (with DC power supply) must be connected in parallel to the coils of these devices.