Xerox DocuPrint 4635 Installation Planning Manual - page 47
PREINSTALLATION
Table 3-8.
System controller and peripheral cabinet
power receptacle requirements
Electrical environment
Voltage
Current
Receptacle
U.S. and Canada 60 Hz
208/240, 1 Phase or
220/230 (L1-L2)
15A
NEMA 6-15R
or ANSI C73,
20R
International 50 Hz
220/2301 Phase
15A
Per local code
50 Hz WYE printer outlet voltages
Note: All power outlets must be dedicated only to this
equipment. Ensure that each power cord has a separate circuit.
50 Hz WYE configurations only: Measure the WYE connection
voltages at the power source. Table 3-9 shows 415 voltages.
Table 3-10 shows 380 and 400 voltages.
Table 3-9.
Printer (50 Hz only) WYE connection for 415 V
Service outlet
Service outlet
configuration
Measurement
Nominal
Range
5 Wire 415 V
Line 1 to Line 2
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 2 to Line 3
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 1 to Line 3
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 1 to Neutral
240 V RMS
216-264 V RMS
5 Wire 415 V
Line 2 to Neutral
240 V RMS
216-264 V RMS
5 Wire 415 V
Line 3 to Neutral
240 V RMS
216-264 V RMS
XEROX 4635 LASER PRINTING SYSTEM INSTALLATION PLANNING GUIDE
3-17