Texts setup:
GECON LITE PLUS sends predefined SMS messages to report what type of event has occured. You can
change these predefined messages that are sent by Gecon. If you would like to see current texts settings, please
send query SMS TEXT to phone number of GECON LITE PLUS.
Example:
abcd TEXT
- get current texts settings
Reply SMS from GECON LITE PLUS will contain object name or event type, and text message after = sign:
OBJ
- object name
AL1 J AL4
- texts for alarm/trouble reports from inputs 1 J 4
RE1 J RE4
- texts for recovery reports from inputs 1 J 4
REP
- text report SMS
You can edit the message by typing the type of report, = sign, and text message after the = sign. # sign has to be
at the end of the setup command. Maximum length of the text is 15 characters.
Example:
abcd AL1=message1# - setup of message about the alarm on input 1
abcd RE3=message2# - setup of message about the recovery on input 3
If you would like to delete a particular message, you can do this by simply putting only the # sign instead of
message. Reports will not be sent.
Example:
abcd RE4=#
- delete the message RE4
Password change:
Default password is abcd. It is highly recommended to change the password immediately.
H=pqcr - command to change password
Example:
abcd h=pqcr SETUP
When putting SETUP at the end, Gecon will confirm you the change with SMS message.
RELAY output:
Gecon contains one switch relay. Relay is normally switched off. You can control it remotely by SMS command or
you can use it for signalization of trouble.
R=OFF - switch off the relay
R=ON - switch on the relay
R=TROUBLE - set the relay to signal the trouble
R=10 - generate 10 seconds impulse [time interval can be 1...60 seconds]
(impulse is understood as change from current status of relay to opposite and back )