Zadako GECON LITE PLUS Installation Manual - page 9
9
Periodical test:
Periodical test is control mechanism to verify if the gateway is functional and connected. Test is performed by
ringing to the first number in the list (T1) in defined time intervals. In case of accepting the call, gateway will close
the call automatically. Periodical test is setup by command
test=time_in_hours
If set to 0, periodical test is switched off. First report is executed one hour after the setup and than regularly in the
defined interval. Maximum interval is 240 hours.
Example:
abcd test=24
- periodical test will be performed every 24 hours
SMS periodical test:
SMS test report is similar control mechanism to check gateway’s functionality.
Report message is sent to the first number in the list (T1). It is set by command
report=interval_in_days
If set to 0, SMS periodical test is switched off. First report is executed 24 hours after the setup and than regularly
in the defined interval.
Example:
abcd report=14
- setup of SMS report with 14 days period
You will receive SMS message „GECON LITE PLUS: report“ to the T1 number.
Practical example:
You can send all commands in one configuration SMS if you follow these rules:
•
SMS needs to begin with 4 characters password
•
Query SMS has to be at the end of the SMS message
•
Commands have to be separated by space
Example:
abcd T1=090xxxxxxx T2=090yyyyyyy VT2=1 IN=AT LOG=CC
| | | | |
| | | | +-- input logic NC / NO
| | | +---------- first input is alarm, second input is trouble
| | |
| | +------------ power cut is reported to only the first number
|
|
| +------------------------ second number
+--------------------------------------- first number
First input is alarm with NC logic, second is trouble with NC logic. Alarm is reported to both numbers, and power
cut is reported to only the first number.