WEG CFW-11 User Manual - page 41
Installation and Connection
3
CFW-11 | 3-15
Model
Frame Size
Power Terminals
Duty
Cycle
Wiring
Fuse I
2
t
@ 25 ºC
[A
2
s]
WEG Recommended
Fuses FNH aR
Knife Contact
WEG
Recommended
Fuses FNHFE aR
Flush End
Terminals
Bolt
(wrench/bolt
head type)
Recommen-
ded
Torque N.m
(lbf.in)
mm
2
AWG
Terminals
Frame Size
In
[A]
Item SAP
Frame Size
In
[A]
Item SAP
CFW110795T4
H
R1/L1,1 - R2/L1,2 -
S1/L2,1 - S2/L2,2 -
T1/L3,1 - T2/L3,2
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60
(531.00)
HD
4 x 120
4 x 4/0
Ring
tongue
1051000 3
2 x
800
10833726 3 1000 12661663
ND
4 x 150
4 x 300
DC+, DC-
M12 (Phillips
hex head)
60
(531.00)
HD/ND 4 in
(2)
102 mm
(2)
M8 (Phillips
hex head)
10 (88.5) HD/ND 2 x 70
2 x 2/0
CFW110877T4
R1/L1,1 - R2/L1,2 -
S1/L2,1 - S2/L2,2 -
T1/L3,1 - T2/L3,2
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60
(531.00)
HD
4 x 120
4 x 4/0
Ring
tongue
1051000 3
2 x
800
10833726 3 1000 12661663
ND
4 x 150
4 x 300
DC+, DC-
M12 (Phillips
hex head)
60
(531.00)
HD/ND 2 x 3 in
(2)
2 x 76 mm
(2)
M8 ( Phillips
hex head)
10 (88.5) HD/ND 2 x 120
2 x 4/0
CFW111062T4
R1/L1,1 - R2/L1,2 -
S1/L2,1 - S2/L2,2 -
T1/L3,1 - T2/L3,2
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60
(531.00)
HD
4 x 150
4 x 300
Ring
tongue
1445000 3
2 x
900
(1)
11393564 3 1250 12661665
ND
4 x 240
4 x 500
DC+, DC-
M12 (Phillips
hex head)
60
(531.00)
HD/ND 2 x 3 in
(2)
2 x 76 mm
(2)
M8 (Phillips
hex head)
10 (88.5) HD/ND 2 x 120
2 x 4/0
CFW111141T4
R1/L1,1 - R2/L1,2 -
S1/L2,1 - S2/L2,2 -
T1/L3,1 - T2/L3,2
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60
(531.00)
HD
4 x 185
4 x 350
Ring
tongue
1445000 3
2 x
900
(1)
11393564 3 1400 12661666
ND
4 x 240
4 x 500
DC+, DC-
M12 (Phillips
hex head)
60
(531.00)
HD/ND 2 x 4 in
(2)
2 x 102 mm
(2)
M8 (Phillips
hex head)
10 (88.5) HD/ND 2 x 150
2 x 300
(1) For this application, the fuse cannot be mounted on the SFWm; only on the individual mounting base.
(2) 1/4-in (6,4mm) copper bus bar must be used with width specified in
Table 3.2 on page 3-13
.