WEG CFW-11 User Manual - page 60
Other manuals for CFW-11:
Programming Manual, Installation And Operation Manual, User Manual, User Manual, Installation Manual
Manual is about: V5.8X
of
116
Installation and Connection
3
3-34 | CFW-11
SRBXX (Safety Stop
board)
XC25
1 (STO1)
(24 Vdc) 13
(DGND*) 11
3 (STO2)
2 (GND1)
4 (GND2)
XC1
CC11 (control board)
Figure 3.19 - Internal control connections to disable Safety Stop function
Table 3.8 - Minimum separation distances between wiring
Cable Length
Minimum Separation
Distance
≤ 30 m (100 ft)
≥ 10 cm (3.94 in)
> 30 m (100 ft)
≥ 25 cm (3.94 in)
4. The correct connection of the cable shield is shown in
Figure 3.20 on page 3-34
and
Figure 3.21 on page
3-35
.
Do not ground
Inverter
side
Insulate with tape
Figure 3.20 - Shield connection