WEG CFW-11 User Manual - page 43
Installation and Connection
3
CFW-11 | 3-17
Model
Frame size
Power terminals
Duty
cycle
Wiring
Fuse
[A]
Fuse I2t
@ 25 ºC
Terminals
[A2s]
Terminals
Bolt
(wrench/bolt
head type)
Recommended
torque N.m
(lbf.in)
mm
2
AWG
Terminais
CFW110795T4DC
H
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD
3 x 150
3 x 300
Ring
tongue
2 x
640
See
note
(2)
ND
3 x 185
3 x 400
DC+, DC-
M12 (Phillips
hex head)
60 (531.00)
HD/ND
4 in
(1)
102 mm
(1)
M8 (Phillips
hex head)
10 (88.5)
HD/ND
185
400
CFW110877T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD
4 x 120
4 x 4/0
Ring
tongue
2 x
830
See
note
(2)
ND
4 x 150
4 x 300
DC+, DC-
M12 (Phillips
hex head)
60 (531.00)
HD/ND 2 x 3 in
(1)
2 x 76mm
(1)
M8 (Phillips
hex head)
10 (88.5)
HD/ND
4 x 120
4 x 4/0
CFW111062T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD
4 x 150
4 x 300
Ring
tongue
2 x
890
See
note
(2)
ND
4 x 240
4 x 500
DC+, DC-
M12 (Phillips
hex head)
60 (531.00)
HD/ND 2 x 3 in
(1)
2 x 76mm
(1)
M8 (Phillips
hex head)
10 (88.5)
HD/ND
2 x 120
2 x 410
CFW111141T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD
2 x 120
2 x 4/0
Ring
tongue
2 x
1035
See
note
(2)
ND
4 x 185
4 x 350
DC+, DC-
M12 (Phillips
hex head)
60 (531.00)
HD/ND 2 x 4 in
(1)
2 x 102mm
(1)
M8 (Phillips
hex head)
10 (88.5)
HD/ND
2 x 150
2 x 300
(1) 1/4-in (6.4mm) copper bus bar must be used with width specified in
Table 3.3 on page 3-16
.
(2) Use fuses with I
2
t value smaller than or equal to the value specified in
Table 3.2 on page 3-13
and voltage and breaking capacity for 800 Vdc.