WEG CFW-11 User Manual - page 82
First Time Power-Up and Start-Up
5
5-4 | CFW-11
Setting the parameters in the Oriented Start-Up routine causes the automatic content modification of the other
parameters and/or internal inverter variables.
During the Oriented Start-up routine, the message "Config" will be displayed at the top left corner of the HMI
display.
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
1 - Monitoring mode
- Press "Menu"
(right soft key)
Ready
LOC
0rpm
13:48
Menu
0
rpm
0.0
A
0.0
Hz
2 - The group "00 ALL
PARAMETERS" is already
selected
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
3 The group "01
PARAMETER GROUPS" is
selected
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
4 - The group "02 ORIENTED
START-UP" is then selected
- Press "Select"
Ready
LOC
0rpm
Return
13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
5 - The parameter "Oriented
Start-up P0317: No" is
already selected
- Press "Select"
Ready
LOC
0rpm
Return
13:48
Select
Oriented Start-Up
P0317: No
6 - The content of "P0317 =
[000] No" is showed
Ready
LOC
0rpm
Return
13:48
Save
P0317
Oriented Start-up
[000] No
7 - The content of the parameter
is changed to "P0317 =
[001] Yes"
- Press "Save"
Ready
LOC
0rpm
Return
13:48
Save
P0317
Oriented Start-up
[001] Yes
8 - At that moment the Oriented
Start-up routine is initiated
and the "Config" status is
indicated at the top left corner
of the HMI
- The parameter "Language
P0201: English" is already
selected
- If necessary, change the
language by pressing "Select",
next
or
to
select the language and then
press "Save"
Config LOC
0rpm
Reset
13:48 Select
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
9 - If necessary, change the
value of P0202 according to
the type of control. To do so,
press "Select"
- The settings listed here are
valid only for
P0202=0 (V/f 60 Hz) or
P0202=1 (V/f 50 Hz). For
other options (Adjustable
V/f, VVW, or Vector
modes), please refer to
the programming manual
Config LOC
0rpm
Reset
13:48 Select
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
10 - If necessary, change the
value of P0296 according to
the line rated voltage
To do so, press "Select"
This modification will affect
P0151, P0153, P0185,
P0321, P0322, P0323, and
P0400
Config LOC
0rpm
Reset
13:48 Select
Type of Control
P0202: V/F 60 HZ
Line Rated Voltage
P0296: 440 - 460 V
11 - If necessary, change the
value of P0298 according to
the inverter application
To do so, press "Select"
This modification will affect
P0156, P0157,P0158, P0401,
P0404 and P0410 (this last
one only if P0202 = 0, 1,
or 2 – V/f control). The time
and the activation level of the
overload protection will be
affected as well
Config LOC
0rpm
Reset
13:48 Select
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
12 - If necessary, change the
value of P0398 according
to the motor service factor
To do so, press "Select"
This modification will affect
the current value and the
activation time of the motor
overload function
Config LOC
0rpm
Reset
13:48 Select
Application
P0298: Heavy Duty
Motor Service Factor
P0398: 1.15