Baldor MicroFlex e100 Installation Manual - page 51
www.baldormotion.com
Feedback 4-11
MN1942
4.1.4 SinCos feedback
The SinCos connections (Sin and Cos incremental channels only) are made using the 15-pin
D-type female connector X8. Twisted pair cables must be used for the complementary signal
pairs e.g. Sin+ and Sin-. The overall cable shield (screen) must be connected to the metallic shell
of the D-type connector. Connector X8 includes a ‘Sense’ pin, which is used to detect the voltage
drop on long cable runs. This allows the MicroFlex e100 to increase the encoder supply voltage
on pin 12 to maintain a 5 V supply at the encoder (200 mA max). The Sin and Cos channel input
circuits accept a nominal 1 V pk-pk sine wave centered on a 2.5 V reference.
Pin SinCos function
1 (NC)
2 (NC)
3 (NC)
4 Sense
5 Sin-
6 Sin+
7 Cos-
8 Cos+
9 (NC)
10 (NC)
11 (NC)
12 +5 V out
13 DGND
14 (NC)
15 (NC)
Sin-
Sin+
Cos-
Cos+
+5 V out
DGND
5
6
7
8
12
X8
SinCos
Feedback
13
4
Sense
Connect overall shield to
connector backshells.
Twisted pairs
Connect internal
shields to DGND.
Motor
Figure 23 - SinCos cable connections
1
8
9
15