Baldor MicroFlex e100 Installation Manual - page 94
www.baldormotion.com
6-14 Configuration
MN1942
save the parameters. Selecting Yes will cause the parameters to be saved in the
MicroFlex e100’s non-volatile flash memory, to be retained when power is removed. If you select
No, you must remember to use the Save Drive Parameters function before removing power from
the MicroFlex e100; this function is available on the Tools menu, or by clicking the
button on
the Mode toolbar. Saving parameters into flash memory will cause the MicroFlex e100 to be
reset.
6.4.3.2 Autotune Wizard
The Autotune Wizard tunes the MicroFlex e100 for optimal performance with the attached
motor. This removes the need for manual fine-tuning of the system, although in some critical
applications this still may be required.
Click Options... to configure optional autotuning parameters. These include Triggered
Autotune which allows the autotuning process to be delayed until the drive is enabled.
The motor will move during autotuning. For safety it is advisable to disconnect any
load from the motor during initial autotuning. The motor can be tuned with the load
connected after the Commissioning Wizard has finished.
Autotune:
Click START to begin the auto-tuning process. Mint WorkBench will take measurements from
the motor and then perform small test moves.
For further information about tuning with the load attached, see section 6.4.5.
CAUTION