6.5.2 connection to circuit breaker
• The circuit breaker NZM4 is equipped with a tunnel terminal per phase.
• The circuit breaker has four connections in two levels.
• Connect the mains cable to terminals L1 / L2 / L3 of the circuit breaker and the PE
conductor to the earthing bar.
• Make sure that the rubber sleeves ensure a clean seal to the used cables.
•
The corresponding cable cross-sections are defined in the technical data.
1 x 50-240 mm²
1 x AWG1/0-500kcmil
4 x 50-240 mm²
4 x AWG1/0-500kcmil
16mm
50Nm
(443lb-in)
f 32mm
(f 1.3“)
30mm
(
1.2“)
55mm
(
2.2“)
8mm
31Nm
(274lb-in)
Figure 24: Connection circuit breaker
Further information about the mains cable are given in the technical data.
56
ELEcTrIcAL INSTALLATION