KEB COMBIVERT F6 Instructions For Use Manual - Attention
7.1.4 Electromagnetic compatibility according to EN 61800-3
EMc emitted interference
Cable-based interferences
–
C3
1) 2)
according to EN55011
Radiated interferences
–
C2
2)
Interference immunity
Static discharges
EN 61000-4-2
8 kV
AD (air discharge) and CD (contact dis-
charge)
Burst - control lines + bus
EN 61000-4-4
2 kV
Burst - mains supply
EN 61000-4-4
4 kV
Surge - mains supply
EN 61000-4-5
1 / 2 kV
Phase-phase / phase-ground
Electromagnetic fields
EN 61000-4-3
10 V/m
Immunity to conducted distur-
bances, induced by radio-fre-
quency fields
EN 61000-4-6
10 V
0.15-80 MHz
MM
Voltage variation /
voltage drop
EN 61000-2-1
3
+10 % -15 %
90 %
Voltage unsymmetries /
Frequency changes
EN 61000-2-4
3
3 %
2 %
Table 6:
Electromagnetic compatibility
1) This product can cause high frequency disturbances in residential areas (category c1) which re-
quire noise suppression measures.
2) The specified value is only meet in connection with a corresponding filter.
7.1.5 Technical data circuit breaker NZM4
Figure 33: Circuit breaker NZM4
Technical data NZM4
Rated continuous current
In
A
1000
Rated short-circuit making capacity
Icm
kA
105
Rated short-circuit breaking capacity
Icu
kA
50
Table 7:
Technical data circuit breaker NZM4
ATTENTION
The warranty expires on change!
The settings at the circuit breaker are preset ex-factory to the respec-
tive system size and sealed.
68
TEcHNIcAL DATA