7.2 Electrical data 690 V mains voltage
Power Drive System
33
37
Mains input
Input rated voltage
U
V AC
600 / 690
Input voltage range
U
in
V AC
360…760 ±0 %
Mains frequency
F
Hz
48-63
Phases
3
permitted mains forms
TN, TT
max. system unbalance
%
8
max. permissible mains short-circuit
current
Icc
kA
50
Input rated power
S
n
kVA
600
980
max. input power
P
n
kW
450
710
Line protection for customer-supplied mains supply line
Fuse
In
A AC
630
-
Circuit breaker
1)
In
A AC
optional
1000
Internal short circuit protection
Circuit breaker
In
A
500
820
Electronic short circuit protection
of the drive converter
In
I
out
%
150
150
Motor output
Output rated power
S
out
kVA
600
980
max. output power
P
out
kW
450
710
Output rated current
I
out
A AC
500
820
max. short time current (E.OL) 30s
2)
I
OL
%
125
125
OC-tripping current (E.OC)
I
OC
%
150
150
Standstill current at 4 kHz
3)
I
dc
A DC
350
570
Output voltage
4)
U
out
V AC
0…Uin
Rated switching frequency
f
S
kHz
4
4
Max. switching frequency
5) f
Smax
kHz
4
4
Output frequency
6)
f
out
Hz
0…max. 599
Min. frequency at continuous full load
f
min
Hz
3
Voltage rise (10-90%)
du/dt
kV/µs
5
Overload characteristic
see => A.1
cable cross-section
Mains connection
mm²
2x120
4x120
Motor cable cross-section
7)
mm²
2x120
1x240
4x120
3x185
2x240
Max. motor line length shielded
M
100
continued on the next page
Table 8:
Technical Data
69