Summary of VEGAPULS 62

  • Page 1

    Operating instructions radar sensor for continuous level measurement of liquids vegapuls 62 hart and accumulator pack document id: 40793.

  • Page 2: Contents

    2 contents vegapuls 62 • hart and accumulator pack 40793-en-170405 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group .................................................

  • Page 3

    3 contents vegapuls 62 • hart and accumulator pack 40793-en-170405 9.2 measured value and event memory ............................................................................... 58 9.3 asset management function .......................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegapuls 62 • hart and accumulator pack 40793-en-170405 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Please...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegapuls 62 • hart and accumulator pack 40793-en-170405 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the...

  • Page 6

    6 2 for your safety vegapuls 62 • hart and accumulator pack 40793-en-170405 2.5 eu conformity thedevicefulfilsthelegalrequirementsoftheapplicableeudirec- tives.Byaffixingthecemarking,weconfirmtheconformityofthe instrument with these directives. Youcanfindtheeuconformitydeclarationonourwebsiteunder w...

  • Page 7

    7 2 for your safety vegapuls 62 • hart and accumulator pack 40793-en-170405 2.8 radio license for usa this approval is only valid for usa. Hence the following text is only available in the english language. This device complies with part 15 of the fcc rules. Operation is subject to the following two...

  • Page 8

    8 2 for your safety vegapuls 62 • hart and accumulator pack 40793-en-170405 installed and maintained to ensure a vertically downward orienta- tion of the transmit antenna's main beam. Furthermore, the use of any mechanism that does not allow the main beam of the transmit- ter to be mounted verticall...

  • Page 9

    9 2 for your safety vegapuls 62 • hart and accumulator pack 40793-en-170405 • environnement ouvert : pour l'utilisation hors des cuves fermées, la condition suivante doit être remplie : l'appareil doit être installé et entretenu de manière à garantir une orientation verticale vers le bas du faisceau...

  • Page 10: 3  Product Description

    10 3 product description vegapuls 62 • hart and accumulator pack 40793-en-170405 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 15 13 14 12 11 5 3 6 4 7 8 10 9 fig. 1: layout of the type label (example) 1 instrument typ...

  • Page 11

    11 3 product description vegapuls 62 • hart and accumulator pack 40793-en-170405 this operating instructions manual applies to the following instrument versions: • hardware from 2.1.0 • software from 4.5.1 theinstrumentisavailableintwodifferentelectronicsversions.Each versioncanbeidentifiedviathepro...

  • Page 12

    12 3 product description vegapuls 62 • hart and accumulator pack 40793-en-170405 the actual values that can be reached depend on the measurement conditions, the antenna system or the standpipe or bypass. The antenna of the radar sensor emits short radar pulses with a durationofapprox.1ns.Thesepulses...

  • Page 13

    13 3 product description vegapuls 62 • hart and accumulator pack 40793-en-170405 3.4 accessories and replacement parts the display and adjustment module plicscom is used for measured value indication, adjustment and diagnosis. It can be inserted into the sensor and removed at any time. The integrate...

  • Page 14: 4 Mounting

    14 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 4 mounting 4.1 general instructions oninstrumentswiththreadedprocessfitting,thehexagonmustbe tightenedwithasuitablewrench.Fortheproperwrenchsizesee chapter "dimensions". Warning: the housing must not be used to screw the instrumen...

  • Page 15

    15 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 prior to setup you have to replace these protective caps with ap- proved cable glands or close the openings with suitable blind plugs. 4.2 mounting preparations the instrument is also available in versions with an antenna whose di...

  • Page 16

    16 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 spring rings according to din 217 or wedge lock washers according to din 25 201. Proceed as follows: 1. Clampvegapuls62withtheflange,e.G.Inabenchvice 2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces (widthacrossflats22mm) ...

  • Page 17

    17 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 4.3 mounting instructions the illustrations with the following mounting instructions show a radar sensor with horn antenna. The mounting instructions apply analo- gously also to the version with parabolic antenna. The emitted rada...

  • Page 18

    18 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 fig. 6: mounting of the radar sensor on vessels with conical bottom donotmounttheinstrumentsinorabovethefillingstream.Makesure thatyoudetecttheproductsurface,nottheinflowingproduct. Fig.7:mountingoftheradarsensorwithinflowingmediu...

  • Page 19

    19 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 > 10 mm (0.39" ) fig. 9: recommended socket mounting with parabolic antenna when using a swivelling holder, keep in mind that the distance between antenna and socket gets smaller as the inclination of the sensorincreases.Additiona...

  • Page 20

    20 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 d h max. Fig. 12: deviating socket dimensions socket diameter d socket length h recommended anten- na diameter 40 mm ≤100mm 40 mm 50 mm ≤150mm 48 mm 80 mm ≤250mm 75 mm 100 mm ≤500mm 95 mm 150 mm ≤800mm 95 mm socket diameter d sock...

  • Page 21

    21 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 proceed as follows to align the sensor with the swivelling holder: 1. Loosen terminal screw of the swivelling holder with a fork spanner sw 13 1 fig. 14: vegapuls 62 with swivelling holder 1 terminal screw information: the hexagon...

  • Page 22

    22 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 interferingreflectionsfromtheagitatorsaresavedwiththebladesin differentpositions. Fig. 16: agitators throughtheactionoffilling,stirringandotherprocessesinthevessel, compact foam can form on the product surface, damping the emitted...

  • Page 23

    23 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 max. 50 mm (1.97" ) 1 2 3 fig. 17: mounting the instrument on insulated vessels. 1 electronics housing 2 spacer 3 vessel insulation 4.4 measurement setup - pipes byusingasurgepipeinthevessel,theinfluenceofvesselinstalla- tions and...

  • Page 24

    24 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 100% 1 2 3 4 5 6 7 1 2 3 98 9 9 10 15° 45° 0% fig.18:configurationsurgepipevegapuls62 1 radar sensor 2 polarisation marking 3 threadorflangeontheinstrument 4 vent hole 5 holes 6 weldingconnectionthroughu-profile 7 ball valve with ...

  • Page 25

    25 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 5 mm (0.20") ø 60,3 mm (2.37") ø 88,9 mm (3.5") ø 114,3 mm (4.5") 4 mm (0.16") 8 mm (0.32") d x 2 d x 2 30,5 mm (1.20") 26 mm (1.02") 15 mm (0.59") 2 mm (0.08") 2 mm (0.08") 2 mm (0.08") 5 mm (0.20") 4 mm (0.16") 100 mm (3.94") 80...

  • Page 26

    26 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 • whenusingaballvalves,alignthetransitionsontheinsideandfix accurately • gapsizewithjunctions≤0.1mm • surge pipes must extend all the way down to the requested min. Level, as measurement is only possible within the tube • diameter...

  • Page 27

    27 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 0 % 100 % 1 2 5 4 3 6 fig.20:configurationbypass 1 radar sensor 2 polarisation marking 3 instrumentflange 4 distance sensor reference plane to upper tube connection 5 distance of the tube connections 6 ball valve with complete ope...

  • Page 28

    28 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 constructional requirements on the bypass pipe: • material metal, smooth inner surface • in case of an extremely rough tube inner surface, use an inserted tube (tube in tube) or a radar sensor with tube antenna • flanges are welde...

  • Page 29

    29 4 mounting vegapuls 62 • hart and accumulator pack 40793-en-170405 2 3 ... 4 x h max 90° h max b 1 fig.22:flowmeasurementwithkhafagi-venturiflume:h max. =max.Fillingofthe flume;b=tightestconstrictionintheflume 1 position sensor 2 venturiflume in general, the following points must be observed: • i...

  • Page 30

    30 5 connecting to power supply vegapuls 62 • hart and accumulator pack 40793-en-170405 5 connecting to power supply 5.1 connection of the battery charger we recommended charging the integrated accumulator completely beforesettinguptheinstrument.Youcanfindthechargingtimein chapter "technical data". ...

  • Page 31

    31 5 connecting to power supply vegapuls 62 • hart and accumulator pack 40793-en-170405 2 4 3 5 0 5 1 6 2 7 3 8 4 9 modes 4 on/off 3 on/off 1h 1,2 off charge accu 5..9 auto cycle 1 2 + ( ) (-) 1 fig. 25: supply room 1 internal connection of the socket for the battery charger 2 mode switch 3 led gree...

  • Page 32

    32 5 connecting to power supply vegapuls 62 • hart and accumulator pack 40793-en-170405 1 fig.26:switchon/offbuttonoutsideonthehousing 1 on/offbutton after switching on, the instrument carries out a self-check for approxi- mately 30 s: • internal check of the electronics • indication of a status mes...

  • Page 33: Module

    33 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 6 set up with the display and adjustment module 6.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchoosea...

  • Page 34

    34 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 1 2 fig. 28: installing the display and adjustment module in the double chamber housing 1 in the electronics compartment 2 in the terminal compartment note: ifyouintendtoretrofittheinstrumentwi...

  • Page 35

    35 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 – move to the menu overview – confirmselectedmenu – edit parameter – save value • [->] key: – change measured value presentation – select list entry – select menu items in the quick setup menu ...

  • Page 36

    36 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 when the [+] and [->] keys are pressed quickly, the edited value, or the cursor, changes one value or position at a time. If the key is pressed longer than 1 s, the value or position changes co...

  • Page 37

    37 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 display: settings, e.G., for language, measured value display, lighting diagnosis: information, e.G. On instrument status, pointer, measure- ment certainty, simulation, echo curve further setti...

  • Page 38

    38 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 through this selection, the sensor is optimally adapted to the product, andmeasurementcertainty,particularlyinproductswithpoorreflec- tive properties, is considerably increased. Enter the reque...

  • Page 39

    39 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 – condensation – smooth product surface – high requirements on measurement accuracy • properties, sensor: – low sensitivity to sporadic false echoes – stable and reliable measured values throug...

  • Page 40

    40 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 – higher measurement speed through less averaging – sporadic false echoes are suppressed dosing vessel: • setup:allvesselsizespossible • medium speed: – fastfillingandemptying – vesselisfilleda...

  • Page 41

    41 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 plastic tank: • vessel: – instrumentfixmountedorbuiltin – measurement through the vessel top, if appropriate to the application – with empty vessel, the measurement can go through the bot- tom ...

  • Page 42

    42 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 rain water overfall (weir): • rate of level change: slow level change • process/measurement conditions: – ice and condensation on the antenna possible – spiders and insects build nests in the a...

  • Page 43

    43 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 enter the requested parameters via the appropriate keys, save your settings with [ok] and jump to the next menu item with the [esc] and the [->] key. Since the radar sensor is a distance measur...

  • Page 44

    44 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 2. Edit the percentage value with [ok] and set the cursor to the requested position with [->]. 3. Set the requested percentage value with [+] and save with [ok]. The cursor jumps now to the dis...

  • Page 45

    45 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 depending on the sensor type, the factory setting is 0 s or 1 s. In the menu item "current output mode" you determine the output characteristics and reaction of the current output in case of fa...

  • Page 46

    46 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 in delivery status, the pin is "0000". This menu item enables the setting of the requested national lan- guage. In delivery status, the sensor is set to the ordered national language. Inthismen...

  • Page 47

    47 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 the respective min. And max. Measured values of the electronics tem- perature are saved in the sensor. These values as well as the current temperature value are displayed in the menu item "peak...

  • Page 48

    48 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 how to interrupt the simulation: → push [esc] information: the simulation is automatically terminated 10 minutes after the last pressing of a key. The "echo curve" shows the signal strength of ...

  • Page 49

    49 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 thefollowingcircumstancescauseinterferingreflectionsandcan influencethemeasurement: • high mounting sockets • vessel internals such as struts • agitators • buildup or welded joints on vessel wa...

  • Page 50

    50 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 if a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "false signal suppression": delete: an already created false signal suppress...

  • Page 51

    51 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 in delivery status, the pin is "0000". In this menu item, the internal clock of the sensor is set. After a reset, certain parameter adjustments made by the user are reset. The following reset f...

  • Page 52

    52 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 menu menu item default value setup measurement loop name sensor medium liquid/water bulk solids/crushed stones, gravel application storage tank silo vessel form vessel bottom, dished form vesse...

  • Page 53

    53 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 in multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address between 1 and 63 must be assigned to each sen- sor. 2) the default setting is standard with address 0. The ...

  • Page 54

    54 6 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 40793-en-170405 in this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the pc. I...

  • Page 55: 7  Setup With Pactware

    55 7 setup with pactware vegapuls 62 • hart and accumulator pack 40793-en-170405 7 setup with pactware 7.1 connect the pc 3 1 2 fig. 32: connection of the pc directly to the sensor via the interface adapter 1 usb cable to the pc 2 interface adapter vegaconnect 3 sensor 7.2 parameter adjustment for p...

  • Page 56

    56 7 setup with pactware vegapuls 62 • hart and accumulator pack 40793-en-170405 fig. 33: example of a dtm view all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already inclu...

  • Page 57

    57 8 set up with other systems vegapuls 62 • hart and accumulator pack 40793-en-170405 8 set up with other systems 8.1 dd adjustment programs device descriptions as enhanced device description (edd) are available for dd adjustment programs such as, for example, ams™ and pdm. Thefilescanbedownloadeda...

  • Page 58

    58 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 9 diagnosis, asset management and service 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 9.2 measured value and event memory the instrument has s...

  • Page 59

    59 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Additionalechocurvesarestoredvia: • pc with pactware/dtm • control system with edd 9.3 asset management fun...

  • Page 60

    60 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 the following table shows the error codes in the status message "failure"andgivesinformationonthereasonandrectification.Keep in mind that some information is only valid for four-wire instruments. Cod...

  • Page 61

    61 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 code text message reason rectification devspec state in cmd 48 f265 measurement func- tion disturbed • sensor no longer carries out a measurement • operating voltage too low • check operating voltage...

  • Page 62

    62 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 code text message reason rectification devspec state in cmd 48 m503 measurement reli- ability too low • the echo/noise ratio is too small for reliable measurement • check installation and process con...

  • Page 63

    63 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 notes: • wherever the sensor displays a constant value, the reason could also be the fault setting of the current output to "hold value" • if the level indication is too low, the reason could be a li...

  • Page 64

    64 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 fault description error pattern reason rectification 6. Measured value re- mains momentarily unchangedduringfill- ing and then jumps to the correct level level time 0 • turbulence on the product surf...

  • Page 65

    65 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 fault description error pattern reason rectification 12. Measured value jumps towards 0 % during emptying level time 0 • echo from the tank bottom larger than the level echo, for example, with produc...

  • Page 66

    66 9 diagnosis, asset management and service vegapuls 62 • hart and accumulator pack 40793-en-170405 9.6 software update the following components are required to update the instrument software: • instrument • voltage supply • interface adapter vegaconnect • pc with pactware • currentinstrumentsoftwa...

  • Page 67: 10 Dismount

    67 10 dismount vegapuls 62 • hart and accumulator pack 40793-en-170405 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters...

  • Page 68: 11 Supplement

    68 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 11 supplement 11.1 technical data note for approved instruments the technical data in the respective safety instructions are valid for approved instruments (e.G. With exapproval).Thesedatacandifferfromthedatalistedherein,forexa...

  • Page 69

    69 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 torques max. Torques, threaded version Ʋ g1½ 200 nm (147.5 lbf ft) max. Torques, antenna system Ʋ mounting screws, antenna cone 2.5 nm (1.8 lbf ft) Ʋ compression nut, parabolic antenna 50 nm (36.89 lbf ft) Ʋ counter nut, parabo...

  • Page 70

    70 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 recommended measuring range Ʋ antenna ø 40 mm (1.575 in) up to 15 m (49.21 ft) Ʋ antenna ø 48 mm (1.89 in) up to 20 m (65.62 ft) Ʋ antenna ø 75 mm (2.953 in), ø 95 mm (3.74 in), parabolic antenna up to 35 m (114.83 ft) electron...

  • Page 71

    71 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 influenceofthesuperimposedgasandpressureonmeasurementaccuracy the propagation speed of the radar impulses in gas or vapour above the medium is reduced by highpressure.Thiseffectdependsonthetypeofsuperimposedgasorvapourandisespe...

  • Page 72

    72 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 Ʋ max. Power density at a distance of 1 m ambient conditions ambient, storage and transport tempera- ture -40 … +80 °c (-40 … +176 °f) process conditions fortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.The...

  • Page 73

    73 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 data on rinsing air connection max. Permissible pressure 6 bar (87.02 psig) air volume with horn antenna, depending on pressure (recommended area) pressure withoutrefluxvalve withrefluxvalve 0.5 bar (7.25 psig) 3.3 m 3 /h 1.2 m...

  • Page 74

    74 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 adjustment elements Ʋ 4 keys [ok], [->], [+], [esc] Ʋ switch bluetoothon/off bluetooth interface Ʋ standard bluetooth smart Ʋ effectiverange 25 m (82.02 ft) protection rating Ʋ unassembled ip 20 Ʋ mounted in the housing without...

  • Page 75

    75 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 external battery charger mains voltage 100 … 240 v ac output voltage 24 v dc max. Output current (short-circuit proof) 500 ma load current limitation 70 ma dc plug (inside plus, outside minus) 2.1 mm integrated accumulator type...

  • Page 76

    76 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 housing 2 1 ø 79 mm (3.11") ~ 84 mm (3.31") m16x1,5 112 mm (4.41") m20x1,5/ ½ npt ~ 87 mm (3.43") m16x1,5 ø 84 mm (3.31") 120 mm (4.72") m20x1,5/ ½ npt fig. 51: dimensions of housing - with integrated display and adjustment mod...

  • Page 77

    77 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls62,hornantennainflangeversion x y 2 1 60 mm (2.36") mm inch 8.50" 16.93" 3.94" ø1.58" ø1.89" ø2.95" ø3.74" 4.72" x y 100 ø40 120 ø48 216 ø75 430 ø95 1½" 2" 3" 4" x y 1½" 2" 3" 4" 166 mm (6.54" ) fig.53:vegapuls62,hornan...

  • Page 78

    78 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls62,hornantennainflangeversionwithpurgingairconnection 22 1 mm inch 8.50" 16.93" 3.94" ø1.58" ø1.89" ø2.95" ø3.74" 4.72" x y 100 ø40 120 ø48 216 ø75 430 ø95 1½" 2" 3" 4" x y 1½" 2" 3" 4" x y x y 3 4 3 4 41,5 mm (1.63") 8...

  • Page 79

    79 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls62,hornantennainflangeversion450°c y x inch 8.50" 11.30" ø 1.89" ø 2.95" ø 3.74" 4.72" mm x y 120 ø 48 216 ø 75 287 ø 95 2" 3" 4" x y 2" 3" 4" 260 mm (10.24") fig.55:vegapuls62,hornantennainflangeversionwithtemperaturea...

  • Page 80

    80 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls 62, horn antenna and swivelling holder 20 mm (0.79") 20 mm (0.79") 40 mm (1.58") max. 15° (0.59") x y x y x y 100 ø 40 120 ø 48 216 ø 75 430 ø 95 1½" 2" 3" 4" x y 1½" 2" 3" 4" 3.94" ø 1.58" ø 1.89" ø 2.95" ø 3.74" 4.72...

  • Page 81

    81 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls62,hornantennaandswivellingholder,threadedfitting 2 1 max. 10° (0.39") 53,6 mm (2.11") 159,6 mm (6.28") 102,2 mm (4.02") ø 40 / 48 mm (1.57" / 1.89" ) g2 / 2npt sw 70 mm (2.76") 102,2 mm (4.02") ø 40 / 48 mm (1.57" / 1....

  • Page 82

    82 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 vegapuls 62, parabolic antenna and swivelling holder 130 mm (5.12") ø 243 mm (9.57") 1 2 40 mm (1.58") max. 15° (0.59") 120 mm (4.72") fig. 58: vegapuls 62, parabolic antenna and swivelling holder 1 standard 2 with temperature ...

  • Page 83

    83 11 supplement vegapuls 62 • hart and accumulator pack 40793-en-170405 11.3 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere in...

  • Page 84: Index

    84 index vegapuls 62 • hart and accumulator pack 40793-en-170405 index a adjustment 43, 44 – system 35 agitator 21 application area 11 b backlight 46 c copy instrument settings 53 current output, min./max. 45 current output mode 45 d damping 44 date/time 51 default values 51 deviation 62 e echo curv...

  • Page 85

    85 notes vegapuls 62 • hart and accumulator pack 40793-en-170405.

  • Page 86

    86 notes vegapuls 62 • hart and accumulator pack 40793-en-170405.

  • Page 87

    87 notes vegapuls 62 • hart and accumulator pack 40793-en-170405.

  • Page 88

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 40793-en-170405 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...