Summary of VEGAPULS 62

  • Page 1

    Quick setup guide radar sensor for continuous level measurement of liquids vegapuls 62 hart and accumulator pack document id: 47110

  • Page 2: Contents

    2 contents vegapuls 62 • hart and accumulator pack 47110-en-140129 contents 1 for your safety 1.1 authorised personnel ....................................................................................................... 3 1.2 appropriate use ..........................................................

  • Page 3: 1  For Your Safety

    3 1 for your safety vegapuls 62 • hart and accumulator pack 47110-en-140129 1 for your safety 1.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the...

  • Page 4

    4 1 for your safety vegapuls 62 • hart and accumulator pack 47110-en-140129 1.5 ce conformity thedevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byaffixingthecemarking,weconfirmsuccessfultestingofthe product. Youcanfindthececertificateofconformityinthedownloadsection of our homepage....

  • Page 5

    5 1 for your safety vegapuls 62 • hart and accumulator pack 47110-en-140129 • chapter "disposal".

  • Page 6: 2  Product Description

    6 2 product description vegapuls 62 • hart and accumulator pack 47110-en-140129 2 product description 2.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 14 15 16 17 13 12 11 5 3 6 4 7 8 9 10 fig. 1: layout of the type label (example) 1 instrumen...

  • Page 7

    7 2 product description vegapuls 62 • hart and accumulator pack 47110-en-140129 • download the smartphone app "vegatools" from the "apple app store" or the "googleplaystore" • scanthedatamatrixcodeonthetypelabeloftheinstrumentor • enter the serial number manually in the app.

  • Page 8: 3 Mounting

    8 3 mounting vegapuls 62 • hart and accumulator pack 47110-en-140129 3 mounting 3.1 mounting preparations - horn antenna the instrument is also available in versions with an antenna whose diameterislargerthantheprocessfitting(thread,flange).Insuch casestheantennamustbedisconnectedfromtheprocessfitti...

  • Page 9

    9 3 mounting vegapuls 62 • hart and accumulator pack 47110-en-140129 2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces (widthacrossflats22mm) 3. Loosen counter nut (3) completely with a wrench (width across flats36mm)inthedirectionoftheantenna 4. Loosen compression nut (2) completely with a w...

  • Page 10

    10 3 mounting vegapuls 62 • hart and accumulator pack 47110-en-140129 ca . 10 mm > 200 mm (7.87") fig. 4: distance of the antenna to the vessel wall/vessel ceiling 2. Note min. Socket diameter depending on the socket length for further information see chapter "mounting"..

  • Page 11

    11 4 connecting to power supply vegapuls 62 • hart and accumulator pack 47110-en-140129 4 connecting to power supply 4.1 connection of the battery charger we recommended charging the integrated accumulator completely beforesettinguptheinstrument.Youcanfindthechargingtimein chapter "technicaldata". T...

  • Page 12

    12 4 connecting to power supply vegapuls 62 • hart and accumulator pack 47110-en-140129 after pressing the key or changing the mode the yellow led shows theaccumulatorstatusforapproximately10sasfollows: • led lights = accumulator is full • ledflashes=accumulatorshouldbecharged • ledoff=accumulatoris...

  • Page 13: Module

    13 5 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 47110-en-140129 5 set up with the display and adjustment module 5.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchoosea...

  • Page 14

    14 5 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 47110-en-140129 1 2 fig. 7: insertion of the display and adjustment module into the double chamber housing 1 in the electronics compartment 2 intheconnectioncompartment(withex-d-iaversionnotpossible) note: ify...

  • Page 15

    15 5 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 47110-en-140129 the radar sensor measures the distance from the sensor to the productsurface.Forindicationofthereallevel,anallocationofthe measured distance to the percentage height must be carried out. 100% 0...

  • Page 16

    16 5 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 47110-en-140129 thefollowingcircumstancescauseinterferingreflectionsandcan influencethemeasurement: • high sockets • vessel installations such as struts • agitators • buildup or welded joints on vessel walls n...

  • Page 17

    17 5 set up with the display and adjustment module vegapuls 62 • hart and accumulator pack 47110-en-140129 the menu item "delete" is used to completely delete an already cre- ated false signal suppression. This is useful if the saved false signal suppression no longer matches the metrological condit...

  • Page 18: 6 Supplement

    18 6 supplement vegapuls 62 • hart and accumulator pack 47110-en-140129 6 supplement 6.1 technical data external battery charger mains voltage 100 … 240 v ac output voltage 24 v dc outputcurrent(shortcircuitproof)max. 500 ma load current limitation 70 ma dcplug(insideplus,outsideminus) 2.1 mm integr...

  • Page 19

    19 notes vegapuls 62 • hart and accumulator pack 47110-en-140129.

  • Page 20

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 471 10-en-140129 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subje...