47110-EN-140129
The radar sensor measures the distance from the sensor to the
productsurface.Forindicationofthereallevel,anallocationofthe
measured distance to the percentage height must be carried out.
100%
0%
0,5
m
(19.68
")
5
m
(196.
9")
2
1
3
Fig. 8: Parameter adjustment example min./max. adjustment
1 Min. level = max. meas. distance
2 Max. level = min. meas. distance
Forthisadjustment,thedistanceisenteredwhenthevesselisfull
andnearlyempty.Ifthesevaluesarenotknown,anadjustmentwith
otherdistances,forexample,10%and90%isalsopossible.Starting
pointforthesedistancespecificationsisalwaysthesealsurfaceof
thethreadorflange.
With the function "Echocurvememory" the echo curve can be saved
at the time of setup. This is generally recommended; for using the As-
setManagementfunctionsitisabsolutelynecessary.Ifpossible,the
curve should be saved with a low level in the vessel.
WiththeadjustmentsoftwarePACTwareandthePC,thehighresolu-
tionechocurvecanbedisplayedandusedtorecognizesignal
changesovertheoperatingtime.Inaddition,theechocurveofthe
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Parameterization example
Diagnostics - Echo curve
memory