    Quick setup guide radar sensor for continuous level measurement of liquids vegapuls 62 4 … 20 ma/hart - four-wire approval according to lpr radio standard document id: 47121.

  • Page 2: Contents

    2 contents vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 contents 1 for your safety 1.1 authorised personnel ....................................................................................................... 3 1.2 appropriate use .........................................................

  • Page 3: 1  For Your Safety

    3 1 for your safety vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 1 for your safety 1.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with th...

  • Page 4

    4 1 for your safety vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 1.5 ce conformity thedevicefulfillsthelegalrequirementsoftheapplicableecguide- lines.Byaffixingthecemarking,weconfirmsuccessfultestingofthe product. Youcanfindthececertificateofconformityinthedownloadsection of our homepage...

  • Page 5

    5 1 for your safety vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 • the mounting location must be at least 4 km away from radio astronomy stations, unless special permission was granted by the responsible national approval authority • when installed within 4 to 40 km of a radio astronomy ...

  • Page 6: 2  Product Description

    6 2 product description vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 2 product description 2.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 15 13 14 12 11 5 3 6 4 7 8 10 9 fig. 1: layout of the type label (example) 1 instrument typ...

  • Page 7: 3 Mounting

    7 3 mounting vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 3 mounting 3.1 mounting preparations the instrument is also available in versions with an antenna whose diameterislargerthantheprocessfitting(thread,flange).Insuch casestheantennamustbedisconnectedfromtheprocessfitting before moun...

  • Page 8

    8 3 mounting vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 spring rings according to din 217 or wedge lock washers according to din 25 201. Proceed as follows: 1. Clampvegapuls62withtheflange,e.G.Inabenchvice 2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces (widthacrossflats22mm) ...

  • Page 9

    9 3 mounting vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 3.2 mounting instructions 1. Distance from the vessel wall > 200 mm, the antenna should protrude > 10 mm into the vessel ca . 10 mm > 200 mm (7.87") fig. 4: distance of the antenna to the vessel wall/vessel ceiling 2. Note min. So...

  • Page 10

    10 4 connecting to power supply vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 4 connecting to power supply 4.1 connection the voltage supply and signal output are connected via the spring- loaded terminals in the housing. Connection to the display and adjustment module or to the interface...

  • Page 11

    11 4 connecting to power supply vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 6. Check the hold of the wires in the terminals by lightly pulling on them 7. Connect the screen to the internal ground terminal, connect the outer ground terminal to potential equalisation in case of power supp...

  • Page 12

    12 4 connecting to power supply vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 power supply 4...20ma active passive common is gnd 5 1 /l /n 2 + ( ) (-) 6 7 8 fig. 7: connection compartment with double chamber housing with low voltage terminal function polarity 1 voltage supply +/l 2 voltag...

  • Page 13: Module

    13 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 5 set up with the display and adjustment module 5.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchoose...

  • Page 14

    14 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 3. Select in the menu item "application" the vessel, the application andthevesselform,forexample,storagetank. 4. Carry out the adjustment in the menu items "min. Adjustment" and "max. Adjustme...

  • Page 15

    15 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 absolutely necessary to do this if you want to use the asset manage- ment functions. If possible, the curve should be saved with a low level in the vessel. With the adjustment software pactwar...

  • Page 16

    16 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 5. All interfering signals in this section are detected by the sensor andstoredafterconfirmingwith[ok]. Note: check the distance to the product surface, because if an incorrect (toolarge)value...

  • Page 17

    17 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 menu item parameter default setting current output mode output character- istics 4 … 20 ma failure mode ≤3.6ma current output - min./max. Min. Current 3.8 ma max.Current 20.5 ma lock adjustmen...

  • Page 18

    18 5 set up with the display and adjustment module vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 menu - info menu item parameter device name vegapuls 6. Instrument version hardware and software version date of manufacture date instrument features order-specificcharacteristics.

  • Page 19: 6 Supplement

    19 6 supplement vegapuls 62 • 4 … 20 ma/hart - four-wire 47121-en-160215 6 supplement 6.1 technical data electromechanical data - version ip 66/ip 67 and ip 66/ip 68; 0.2 bar options of the cable entry Ʋ cable entry m20x1.5,½npt Ʋ cable gland m20x1,5;½npt(cableøseebelowtable) Ʋ blind plug m20x1.5;½n...

  • Page 20

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 47121-en-160215 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...