WEG CFW-11 User Manual - page 48
Installation and Connection
3
CFW-11 | 3-27
Connector XC1 Factory Default Function
Specifications
1
+REF Positive reference for
potentiometer
Output voltage:+5.4 V, ±5 %
Maximum output current: 2 mA
2
AI1+ Analog input 1:
speed reference (remote)
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
IN
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
= 500 Ω)
Maximum voltage: ±30 V
3
AI1-
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %
Maximum output current: 2 mA
5
AI2+ Analog input 2:
no function
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
IN
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
= 500 Ω)
Maximum voltage: ±30 V
6
AI2-
7
AO1
Analog output 1:
speed
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
≤ 500 Ω)
Protected against short-circuit
8
AGND
(24 V)
Reference (0 V) for the analog
outputs
Connected to the ground (frame) through an impedance: 940 Ω resistor
in parallel with a 22 nF capacitor. Same reference as the one of DGND *
9
AO2
Analog output 2:
motor current
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
≤ 500 Ω)
Protected against short-circuit
10
AGND
(24 V )
Reference (0 V) for the analog
outputs
Connected to the ground (frame) through an impedance: 940 Ω resistor
in parallel with a 22 nF capacitor. Same reference as the one of DGND *
11
DGND* Reference (0 V) for the 24 Vdc
power supply
Connected to the ground (frame) through an impedance: 940 Ω resistor
in parallel with a 22 nF capacitor. Same reference as the one of AGND (24 V)
12
COM Common point of the digital
inputs
13
24 Vdc 24 Vdc power supply
24 Vdc power supply, ±8 %
Capacity: 500 mA
Note: In the models with the 24 Vdc external control power supply
(CFW11...O...W...) pin 13 o XC1 is considered na input, that is, the user
must provide a supply for the inverter (for further details refer to
24 Vdc External Control Power Supply on page 7-2
for more details). In
all the other models this terminal is an output, i.e., the user has a 24 Vdc
power supply available there
14
COM Common point of the digital
inputs
15
DI1
Digital input 1:
Start/Stop
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @ 24 Vdc
16
DI2
Digital input 2:
direction of rotation (remote)
17
DI3
Digital input 3:
no function
18
DI4
Digital input 4:
no function
19
DI5
Digital input 5:
Jog (remote)
20
DI6
Digital input 6:
2
nd
ramp
21
NC1
Digital output 1 DO1 (RL1):
no fault
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - normally closed contact
C - common
NO - normally open contact
22
C1
23
NO1
24
NC2
Digital output 2 DO2 (RL2):
N > N
X
- Speed > P0288
25
C2
26
NO2
27
NC3
Digital output 3 DO3 (RL3):
N* > N
X
- Speed reference
> P0288
28
C3
29
NO3
CCW
CW
≥5 kΩ
rpm
amp
(b) Digital inputs working as "active low"
Figure 3.19 - (a) and (b) - Signals at connector XC1