WEG CFW-11 User Manual - page 74
First Time Power-Up and Start-Up
5
CFW-11 | 5-5
5.2.3 Setting Basic Application Parameters
After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a number of other parameters that allow its adaptation to the most different applications. This
manual presents some basic parameters, whose setting is necessary in the majority of cases. To make this task
easier, there is a group named Basic Application. A summary of the parameters inside this group is listed in
. There is also a group of read only parameters that shows the value of the most important
. For further details, please refer to the CFW-11 programming manual.
Follow steps outlined in
to set the parameters of the Basic Application group.
The procedure for start-up in the V/f operation mode is finished after setting these parameters.
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
1 - Monitoring mode
- Press "Menu"
(right soft key)
Ready
LOC
0rpm
15:45
Menu
0
rpm
0.0
A
0.0
Hz
2
- Group "00
ALL PARAMETERS" has been
already selected
Ready
LOC
0rpm
Return
15:45
Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
3 - Group "01
PARAMETER GROUPS" is
then selected
Ready
LOC
0rpm
Return
15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
4
- Group "02
ORIENTED START-UP" is
then selected
Ready
LOC
0rpm
Return
15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
5 - Group "03
CHANGED PARAMETERS" is
selected
Ready
LOC
0rpm
Return
15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
6
- Group "04 BASIC
APPLICATION" is selected
- Press "Select"
Ready
LOC
0rpm
Return
15:45 Select
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
04 BASIC APPLICATION
7 - Parameter "Acceleration
Time P0100: 20.0 s" has
been already selected
- If needed, set P0100
according to the desired
acceleration time. To do so,
press "Select"
- Proceed similarly until all
parameters of group "04
BASIC APPLICATION" have
been set. When finished,
press "Return" (left soft key)
Ready
LOC
0rpm
Return
15:45 Select
Acceleration Time
P0100: 20.0s
Deceleration Time
P0101: 20.0s
8
- Press "Return"
Ready
LOC
0rpm
Return
15:45 Select
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
04 BASIC APPLICATION
9 - The display returns to the
Monitoring mode and the
inverter is ready to run
Ready
LOC
0rpm
15:45
Menu
0
rpm
0.0
A
0.0
Hz
Figure 5.3 - Setting parameters of the Basic Application group