Installation and Connection
3
CFW-11 | 3-29
Frame size E inverters - SRB4.00 board
Figure 3.21 - SRBXX board connections (Safety Stop function)
Table 3.8 - Minimum separation distances between wiring
Cable Length
Minimum Separation
Distance
≤ 30 m (100 ft)
≥ 10 cm (3.94 in)
> 30 m (100 ft)
≥ 25 cm (9.84 in)
4. The adequate connection of the cable shield is shown in
shows how to connect the cable shield to the ground.