WEG CFW-11 User Manual - page 88
Troubleshooting and Maintenance
6
CFW-11 | 6-9
6.4 INFORMATION FOR CONTACTING TECHNICAL SUPPORT
NOTE!
For technical support and servicing, it is important to have the following information in hand:
Inverter model.
Serial number, manufacturing date, and hardware revision that are listed in the product nameplate
(refer to
Section 2.4 IDENTIFICATION LABELS FOR THE CFW-11 on page 2-7
Installed software version (check parameter P0023).
Application data and inverter settings.
6.5 PREVENTIVE MAINTENANCE
DANGER!
Always turn off the mains power supply before touching any electrical component associated to
the inverter.
High voltage may still be present even after disconnecting the power supply.
To prevent electric shock, wait at least 10 minutes after turning off the input power for the
complete discharge of the power capacitors.
Always connect the equipment frame to the protective ground (PE). Use the adequate connection
terminal in the inverter.
DANGER!
Débranchez toujours l'alimentation principale avant d'entrer en contact avec un appareil électrique
associé au variateur.
Des tensions élevées peuvent encore être présentes, même après déconnexion de l’alimentation.
Pour éviter les risques d’électrocution, attendre au moins 10 minutes après avoir coupé
l’alimentation d’entrée pour que les condensateurs de puissance soient totalement déchargées.
Raccordez toujours la masse de l'appareil à une terre protectrice (PE). Utiliser la borne de
connexion adéquate du variateur.
ATTENTION!
The electronic boards have electrostatic discharge sensitive components.
Do not touch the components or connectors directly. If necessary, first touch the grounded mettalic
frame or wear a ground strap.
Do not perform any withstand voltage test!
If necessary, consult WEG.
The inverters require low maintenance when properly installed and operated. The
presents main procedures and time intervals for preventive maintenance. The
recommended periodic inspections to be performed every 6 months after inverter start-up.