WEG CFW-11 User Manual - page 73
First Time Power-Up and Start-Up
5
5-4 | CFW-11
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
9
- If needed, change the value
of P0202 according
to the type of control. To do
so, press "Select"
- The settings listed here are valid
only for P0202 = 0 (V/f 60
Hz) or P0202 = 1 (V/f 50 Hz).
For other options (Adjustable
V/f, V V W, or Vector
modes), please refer to the
programming manual
Config LOC
0rpm
Reset
13:48 Select
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
10 - If needed, change the
value of P0296 according
to the line rated voltage.
To do so, press "Select".
This modification will
affect P0151, P0153,
P0185, P0321, P0322,
P0323, and P0400
Config LOC
0rpm
Reset
13:48 Select
Type of Control
P0202: V/F 60 HZ
Line Rated Voltage
P0296: 440 - 460 V
11 - If needed, change the value
of P0298 according to the
inverter application. To do
so, press "Select"
This modification will affect
P0156, P0157, P0158,
P0401, P0404 and P0410
(this last one only if P0202
= 0, 1, or 2 – V/f control)
The time and the activation
level of the overload
protection will be affected
as well
Config LOC
0rpm
Reset
13:48 Select
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
12 - If needed, change the
value of P0398 according
to the motor service factor.
To do so, press "Select".
This modification will affect
the current value and the
activation time of the motor
overload function
Config LOC
0rpm
Reset
13:48 Select
Application
P0298: Heavy Duty
Motor Service Factor
P0398: 1.15
13 - If needed, change the value
of P0400 according to the
motor rated voltage. To
do so, press "Select". This
modification adjusts the
output voltage by a factor x
= P0400/P0296
Config LOC
0rpm
Reset
13:48 Select
Motor Service Factor
P0398: 1.15
Motor Rated Voltage
P0400: 440 V
14 - If needed, change the
value of P0401 according
to the motor rated current.
To do so, press "Select".
This modification will affect
P0156, P0157, P0158, and
P0410
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 13.5 A
15 - If needed, set P0402
according to the motor
rated speed. To do so, press
"Select". This modification
affects P0122 to P0131,
P0133, P0134, P0135,
P0182, P0208, P0288, and
P0289
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Current
P0401: 13.5 A
Motor Rated Speed
P0402: 1750 rpm
16 - If needed, set P0403
according to the motor
rated frequency. To do
so, press "Select". This
modification affects
P0402
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Speed
P0402: 1750 rpm
Motor Rated Frequency
P0403: 60 Hz
17 - If needed, change the
value of P0404 according to
the motor rated power
To do so, press "Select"
This modification affects
P0410
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 30hp 22kW
18 - This parameter will only be
visible if the encoder board
ENC1 is installed in the
inverter
- If there is an encoder
connected to the motor, set
P0405 according to the
encoder pulses number. To
do so, press "Select"
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Power
P0404: 4hp 3kW
Encoder Pulses Number
P0405: 1024 ppr
19 - If needed, set P0406
according to the motor
ventilation. To do so, press
"Select"
- To complete the Oriented
Start-Up routine, press
"Reset"
(left soft key) or
.
Config LOC
0rpm
Reset
13:48 Select
Encoder Pulses Number
P0405: 1024 ppr
Motor Ventilation
P0406: Self-Vent.
20 - After few seconds, the
display returns to the
Monitoring mode
Ready
LOC
0rpm
13:48
Menu
0
rpm
0.0
A
0.0
Hz
Figure 5.2 - Oriented Start-up