KEB COMBIVERT F5 Installation Manual - Annex B
Annex B
GB - 28
B.
Annex B
B.1 CE-Marking
CE marked frequency inverter and servo drives were developed and manufactured to comply
with the regulations of the Low-Voltage Directive 2006/95/EC.
The inverter or servo drive must not be started until it is determined that the installation
complies with the Machine directive (2006/42/EC) as well as the EMC-directive (2004/108/
EC)(note EN 60204).
The frequency inverters and servo drives meet the requirements of the Low-Voltage Directive
2006/95/EC. The harmonized standards of the series EN 61800-2 were used.
This is a product of limited availability in accordance with IEC 61800-3. This product may
cause radio interference in residential areas. In this case the operator may need to take
corresponding measures.
B.2 UL Marking
Acceptance according to UL is marked at KEB inverters with the adjacent
logo on the type plate.
To be conform according to UL for use on the North American Market the following
instructions must be observed (original text of the UL-File):
•
For 240 V Models, stand-alone drive units:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms
Symmetrical Amperes, 240 Volts Maximum, when Protected by Fuses, see Instruc-
tion Manual for specific fuse details and alternate Branch Circuit Protection details”
•
For 480 V Models, stand-alone drive units:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms
Symmetrical Amperes, 480 Volts Maximum, when Protected by Fuses, see Instruc-
tion Manual for specific fuse details and alternate Branch Circuit Protection Details”
•
Maximum Surrounding Air Temperature 45 °C (113 °F)
•
For control cabinet mounting as „Open Type“
•
Use in a pollution degree 2 environment
•
Use 60/75°C Copper Conductors Only
•
Internal Overload Protection Operates prior to reaching the 130% of the inverter output
rated current (see type plate). Motor protection by adjustment of current parameters.
For adjustement see application manual parameters Pn.14 and Pn.15.
•
Motor Overtemperature Protection:
These drive models are not provided with load and speed sensitive overload protection
and thermal memory retention up on shutdown or loss of power (for details see NEC,
article 430.126(A)(2)”.
•
Only for use in WYE 480V/277V supply sources
•
Operator and Control Board Rating of relays (30Vdc.:1A)