Installation Manual, Instruction Manual, Instruction Manual, Instructions For Use Manual, Instructions For Use Manual, Instruction manual, Installation Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instructions For Use Manual, Instruction Manual, Instruction Manual, Safety Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instructions for use manual, Instruction Manual, Instruction Manual, Instruction Manual, Instructions For Use Manual, Instruction Manual, Instruction Manual, Installation Manual, Instruction Manual
Manual is about: ELEVATOR DRIVE
of
16
11
Description of the Interface
Clock signal
Data
Monoflop
Position data
P: Parallel position data
T: Period
Tp: Clock interruption up to the next request
tm:
Pulse duration of the monoflop
tv: Deceleration time
D
high
:
Most significant position bit
D
low
:
Least significant position bit
Figure 4:
Serial data transmission with SSI encoder
3.4.2.2 Encoder breakage recognition
An error bit is evaluated for monitoring of the encoder at channel 2. The monitoring is switched
on/off with parameter Ec.42 (Ec.20 up to V2.8). The encoder breakage recognition triggers an
„error! encoder 2“ (value 34).
For encoder breakage detection the encoder needs to send a so-called Power failure bit and
the evaluation with Ec24 "SSI power failure bit" has to be enabled.