Vega VEGAPULS 62 Operating Instructions Manual - page 75
75
11 Supplement
VEGAPULS 63 • Modbus and Levelmaster protocol
41364-EN-170711
Gas phase
Temperature
Pressure
1 bar
(14.5 psig)
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
Air
20 °C/68 °F
0 %
0.22 %
1.2 %
2.4 %
4.9 %
200 °C/392 °F -0.01 %
0.13 %
0.74 %
1.5 %
3 %
400 °C/752 °F -0.02 %
0.08 %
0.52 %
1.1 %
2.1 %
Hydrogen
20 °C/68 °F
-0.01 %
0.10 %
0.61 %
1.2 %
2.5 %
200 °C/392 °F -0.02 %
0.05 %
0.37 %
0.76 %
1.6 %
400 °C/752 °F -0.02 %
0.03 %
0.25 %
0.53 %
1,1 %
Steam (satu-
rated steam)
100 °C/212 °F 0.26 %
-
-
-
-
180 °C/356 °F 0.17 %
2.1 %
-
-
-
264 °C/507 °F 0.12 %
1.44 %
9.2 %
-
-
366 °C/691 °F 0.07 %
1.01 %
5.7 %
13.2 %
76 %
Characteristics and performance data
Measuring frequency
K-band(26GHztechnology)
Measuring cycle time
Ʋ Standard electronics approx.
450 ms
Ʋ Electronics with increased sensitivity
approx.
700 ms
Step response time
3)
≤3s
Beam angle
4)
Ʋ Clamp 2", 3"
18°
Ʋ Clamp 3½", 4"
10°
Ʋ Slotted nut DN 50
18°
Ʋ Slotted nut DN 80
10°
Ʋ Flange DN 50, ASME 2"
18°
Ʋ Flange DN 80 … DN 150,
ASME 3" … 6"
10°
Emitted HF power (depending on the parameter setting)
5)
Ʋ Average spectral transmission power
density
-14dBm/MHzEIRP
Ʋ Max. spectral transmission power
density
+43dBm/50MHzEIRP
Ʋ Max. power density at a distance of
1 m
< 1 µW/cm²
3)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solidsapplications,untiltheoutputsignalhastakenforthefirsttime90%ofthefinalvalue(IEC61298-2).
4)
Outsidethespecifiedbeamangle,theenergyleveloftheradarsignalis50%(-3dB)less.
5)
EIRP: Equivalent Isotropic Radiated Power.
Summary of VEGAPULS 62
Page 1
Operating instructions radar sensor for continuous level measurement of liquids vegapuls 63 modbus and levelmaster protocol document id: 41364.
Page 2: Contents
2 contents vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group ...........................................
Page 3
3 contents vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 8.2 parameter adjustment .................................................................................................... 60 8.3 saving the parameterisation data ................................................................
Page 4: 1 About This Document
4 1 about this document vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenance,faultrectification,th...
Page 5: 2 For Your Safety
5 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and wi...
Page 6
6 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 depending on the instrument version, the emitting frequencies are in the c, k or w band range. The low emission power is far below the internationally approved limit values. When used correctly, the device poses no dan...
Page 7
7 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 • flanges,processfittingsandmountingaccessoriesmustensure the microwave impermeability of the vessel and not let the radar signal escape to the outside • if necessary, existing viewing windows in the vessel must be coa...
Page 8
8 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 this device has been approved for both closed containers and open- air environments with the following limitations: • closedcontainers:forinstallationsutilizingatiltduringinstalla- tion: this device is limited to insta...
Page 9
9 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 • cuves fermées : pour les installations impliquant une inclinaison lors de l'installation : cet appareil ne doit être installé que dans une cuve totalement fermée en en métal, en béton ou en matière plas- tiqerenforcé...
Page 10
10 2 for your safety vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 installations in canada shall comply with the relevant requirements of the canadian electrical code 2.11 environmental instructions protection of the environment is one of our most important duties. That is why we hav...
Page 11: 3 Product Description
11 3 product description vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 15 13 14 12 11 5 3 6 4 7 8 10 9 fig. 1: layout of the type label (example) 1 instrume...
Page 12
12 3 product description vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 theinstrumentcontainstwodifferentelectronicsinitshousingcham- bers: • the modbus electronics for power supply and communication with the modbus-rtu • the sensor electronics for the actual measuring tasks 2 1 fig. ...
Page 13
13 3 product description vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 3.2 principle of operation the vegapuls 63 is a radar sensor for continuous level measure- ment of aggressive liquids or with hygienic requirements. It is suitable for applications in storage tanks, process vessel...
Page 14
14 3 product description vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 with an instrument weight of more than 18 kg (39.68 lbs) suitable and approved equipment must be used for lifting and carrying. 3.4 accessories and replacement parts the display and adjustment module plicscom is u...
Page 15: 4 Mounting
15 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 4 mounting 4.1 general instructions oninstrumentswiththreadedprocessfitting,thehexagonmustbe tightenedwithasuitablewrench.Fortheproperwrenchsizesee chapter "dimensions". Warning: the housing must not be used to screw the ins...
Page 16
16 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 you have to remove these plugs before electrical connection. Npt thread in the case of instrument housings with self-sealing npt threads, it is not possible to have the cable entries screwed in at the factory. The free openi...
Page 17
17 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 note: it is recommended, retightening the screws in regular intervals depending on process pressure and temperature. Recommended torque (see chapter "technical data"). The emitted radar impulses of the radar sensor are elect...
Page 18
18 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 in vessels with conical bottom it can be advantageous to mount the sensor in the centre of the vessel, as measurement is then possible down to the bottom. Fig. 6: mounting of the radar sensor on vessels with conical bottom t...
Page 19
19 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 fig.8:mountingoftheradarsensorwithinflowingmedium flush mounting the best way to mount the sensor, also with respect to cleanability, isflushonablockflange(flangewithoutsocketpiece)orthrougha hygienicfitting. Mounting on soc...
Page 20
20 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 socket diameter d socket length h 150 mm ≤500mm socket diameter d socket length h 2" ≤3.9in 3" ≤11.8in 4" ≤15.8in 6" ≤19.7in in liquids, direct the sensor as perpendicular as possible to the prod- uct surface to an achieve o...
Page 21
21 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 fig. 12: agitators throughtheactionoffilling,stirringandotherprocessesinthevessel, compact foam can form on the product surface, damping the emitted signals considerably. If foams are causing measurement errors, the biggest ...
Page 22
22 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 100% 1 2 3 4 5 6 8 9 10 7 15° 45° 0% fig.13:configurationsurgepipevegapuls63 1 radar sensor 2 polarisation marking 3 threadorflangeontheinstrument 4 vent hole 5 holes 6 weldingconnectionthroughu-profile 7 ball valve with com...
Page 23
23 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 ø 60,3 mm (2.37") ø 88,9 mm (3.5") d x 2 26 mm (1.02") 15 mm (0.59") 2 mm (0.08") 2 mm (0.08") 5 mm (0.20") 4 mm (0.16") 80 mm (3.15") 80 mm (3.15") 75° 4 mm (0.16") 8 mm (0.32") 75° 4 mm (0.16") 8 mm (0.32") d x 2 ø 88,9 mm...
Page 24
24 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 constructive requirements: • material metal, smooth inner surface • preferably pultruded or straight beaded stainless steel tube • welded joint should be straight and lie in one axis with the holes • flanges are welded to th...
Page 25
25 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 0 % 100 % 1 2 5 4 3 6 fig.15:configurationbypass 1 radar sensor 2 polarisation marking 3 instrumentflange 4 distance sensor reference plane to upper tube connection 5 distance of the tube connections 6 ball valve with comple...
Page 26
26 4 mounting vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 constructional requirements on the bypass pipe: • material metal, smooth inner surface • in case of an extremely rough tube inner surface, use an inserted tube (tube in tube) or a radar sensor with tube antenna • flanges are...
Page 27: System
27 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 5 connecting to power supply and bus system 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. ...
Page 28
28 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 make sure that the cable screen and grounding are carried out ac- cordingtofieldbusspecification.Werecommendtoconnectthe cable screen to ground potential on both ends. In systems with potenti...
Page 29
29 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithout end sleeves, press the terminal from above with a small...
Page 30
30 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 5 6 7 8 4...20ma 2 1 2 + ( ) (-) 1 1 fig. 18: electronics compartment - double chamber housing 1 internal connection to the terminal compartment 2 for display and adjustment module or interfa...
Page 31
31 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 5.4 double chamber housing with vegadis-adapter 3 1 2 fig. 20: view to the electronics compartment with vegadis adapter for connec- tion of the external display and adjustment unit 1 vegadis ...
Page 32
32 5 connecting to power supply and bus system vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 then the actual measured value is outputted to the signal cable. The value takes into account settings that have already been carried out, e.G. Default setting..
Page 33: Adjustment Module
33 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 6 set up the sensor with the display and adjustment module 6.1 adjustment volume the display and adjustment module is only used for parameter adjust- ment of the sensor, i.E. F...
Page 34
34 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 6.3 adjustment system 1 2 fig. 23: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confirmselectedmenu – edit parameter...
Page 35
35 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 1 2 4 5 3 fig. 24: display and adjustment elements - with adjustment via magnetic pen 1 lc display 2 magnetic pen 3 adjustment keys 4 bluetooth symbol 5 lid with inspection win...
Page 36
36 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 this menu item is used to select the national language for further pa- rameter adjustment. You can change the selection via the menu item "setup - display, menu language". With...
Page 37
37 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 nationmustbeenteredforexactidentificationofindividualmeasuring points. The available digits include: • letters from a … z • numbers from 0 … 9 • special characters +, -, /, - e...
Page 38
38 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 the selection "standpipe" opens a new window in which the inner diameter of the applied standpipe is entered. Following the characteristics of the applications and the metrolog...
Page 39
39 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 – high sockets 200 … 500 mm, also with large diameters • process/measurement conditions: – condensation, buildup by movement – max. Requirement on measurement accuracy from 95 ...
Page 40
40 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 – entering the tube inside diameter takes the running time shift into consideration – echo detection sensitivity reduced bypass: • medium speed: – fastuptoslowfillingwithshortu...
Page 41
41 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 – extreme damping of output signal due to wave generation – ice and condensation on the antenna possible – spiders and insects build nests in the antennas – floating material a...
Page 42
42 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 if you want to measure the total height of both liquids reliably, please contact our service department or use an instrument specially de- signed for interface measurement. Apa...
Page 43
43 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 100% 0% 0,5 m (19.68 ") 5 m (196.9 ") 2 1 3 fig. 25: parameterisation example, min./max. Adjustment 1 min. Level = max. Measuring distance 2 max. Level = min. Measuring distanc...
Page 44
44 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 4. Enter the suitable distance value in m for empty vessel (e.G. Dis- tance from the sensor to the vessel bottom) corresponding to the percentage value. 5. Save settings with [...
Page 45
45 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 the default setting is output characteristics 4 … 20 ma, fault mode in the menu item "current output min./max.", you determine the reac- tion of the current output during opera...
Page 46
46 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 in delivery status, the sensor is set to the ordered national language. Inthismenuitemyoucandefinetheindicationofthemeasuredvalue on the display. The default setting for the in...
Page 47
47 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 when non-contact level sensors are used, the measurement can be influencedbytherespectiveprocessconditions.Inthismenuitem, the measurement certainty of the level echo is displa...
Page 48
48 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 the "false signal suppression" displays the saved false echoes (see menu "additional settings") of the empty vessel with signal strength in "db" over the entire measuring range...
Page 49
49 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 note: a false signal suppression detects, marks and saves these false signals to ensure that they are ignored in the level measurement. This should be done with the lowest poss...
Page 50
50 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 too high a level and not all false signals could be detected. When selecting "extend", the distance to the product surface of the created false signal suppression is displayed....
Page 51
51 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 after a reset, certain parameter adjustments made by the user are reset. The following reset functions are available: delivery status: restores the parameter settings at the ti...
Page 52
52 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 menu menu item default value display language like order displayed value distance display unit m scalingsize volume l scaling 0.00 lin %, 0 l 100.00 lin %, 100 l backlight swit...
Page 53
53 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 the copied data are permanently saved in an eeprom memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written i...
Page 54
54 6 set up the sensor with the display and adjustment module vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 6.6 saving the parameterisation data we recommended writing down the adjustment data, e.G. In this op- erating instructions manual, and archiving them afterwards. They are thus...
Page 55: With Pactware
55 7 setting up sensor and modbus interface with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 7 setting up sensor and modbus interface with pactware 7.1 connect the pc connection of the pc to the sensor electronics is carried out via the interface adapter vegaconnect. Scope...
Page 56
56 7 setting up sensor and modbus interface with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 1 fig. 27: connecting the pc via usb to the modbus electronics 1 usb cable to the pc connection of the pc to the rs 485 cable is carried out via a stand- ard interface adapter rs 4...
Page 57
57 7 setting up sensor and modbus interface with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 tion. The dtms can also be integrated into other frame applications according to fdt standard. Note: to ensure that all instrument functions are supported, you should always use th...
Page 58
58 7 setting up sensor and modbus interface with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 7.3 set instrument address the vegapuls 63 requires an address for participating as a slave in the modbus communication. The addess setting is carried out via a pc with pactware/dt...
Page 59
59 7 setting up sensor and modbus interface with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 7.4 saving the parameterisation data we recommend documenting or saving the parameterisation data via pactware. That way the data are available for multiple use or service purposes...
Page 60: 8 Setup With Pactware
60 8 setup with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 8 setup with pactware 8.1 connect the pc 3 1 2 fig. 30: connection of the pc directly to the sensor via the interface adapter 1 usb cable to the pc 2 interface adapter vegaconnect 3 sensor 8.2 parameter adjustment...
Page 61
61 8 setup with pactware vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 fig. 31: example of a dtm view all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already...
Page 62
62 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 9 diagnosis, asset management and service 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 9.2 measured value and event memory the instrument...
Page 63
63 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Additionalechocurvesarestoredvia: • pc with pactware/dtm • control system with edd 9.3 asset manageme...
Page 64
64 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 the following table shows the codes and text messages of the status message "failure" and provides information on causes as well as corrective measures. Code text message reason rectification d...
Page 65
65 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 code text message reason rectification devspec diagnosis bits f265 measurement func- tion disturbed • sensor no longer carries out a measurement • operating voltage too low • check operating vo...
Page 66
66 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 code text message reason rectification devspec state in cmd 48 m503 measurement reli- ability too low • the echo/noise ratio is too small for reliable measurement • check installation and proce...
Page 67
67 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 notes: • wherever the sensor displays a constant value, the reason could also be the fault setting of the current output to "hold value" • if the level indication is too low, the reason could b...
Page 68
68 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 fault description error pattern reason rectification 6. Measured value re- mains momentarily unchangedduringfill- ing and then jumps to the correct level level time 0 • turbulence on the produc...
Page 69
69 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 fault description error pattern reason rectification 12. Measured value jumps towards 0 % during emptying level time 0 • echo from the tank bottom larger than the level echo, for example, with ...
Page 70
70 9 diagnosis, asset management and service vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 9.6 software update the following components are required to update the instrument software: • instrument • voltage supply • interface adapter vegaconnect • pc with pactware • currentinstrument...
Page 71: 10 Dismount
71 10 dismount vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of ch...
Page 72: 11 Supplement
72 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 11 supplement 11.1 technical data note for approved instruments the technical data in the respective safety instructions are valid for approved instruments (e.G. With exapproval).Thesedatacandifferfromthedatalistedherein,...
Page 73
73 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 Ʋ aluminium/stainless steel housing 50 nm (36.88 lbf ft) input variable measured variable the measured quantity is the distance between the end of the sensor antenna and the product surface. The reference plane for the me...
Page 74
74 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 Ʋ busspecifications modbus application protocol v1.1b3, modbus over se- rial line v1.02 Ʋ data protocols modbus rtu, modbus ascii, levelmaster max. Transmission rate 57.6 kbit/s accuracy (according to din en 60770-1) proc...
Page 75
75 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 gas phase temperature pressure 1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig) 100 bar (1450 psig) 200 bar (2900 psig) air 20 °c/68 °f 0 % 0.22 % 1.2 % 2.4 % 4.9 % 200 °c/392 °f -0.01 % 0.13 % 0.74 % 1.5 % 3 % 400 °...
Page 76
76 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 ambient conditions ambient, storage and transport tempera- ture -40 … +80 °c (-40 … +176 °f) process conditions thefollowingspecificationsareforinformation.Thespecificationsonthetypeplatemustbenoted. Process temperature a...
Page 77
77 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 electromechanical data - version ip 66/ip 67 cable gland m20 x 1.5 or ½ npt wire cross-section (spring-loaded terminals) Ʋ massive wire, stranded wire 0.2 … 2.5 mm² (awg 24 … 14) Ʋ stranded wire with end sleeve 0.2 … 1.5 ...
Page 78
78 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 additional output parameter - electronics temperature output of the values Ʋ analogue via the current output Ʋ digital via the digital output signal (depending on the electron- ics version) range -40 … +85 °c (-40 … +185 ...
Page 79
79 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 pollution degree 6) 4 protection rating (iec 61010-1) iii approvals instrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion. For that reason the associated approval documents of these instrume...
Page 80
80 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 protocol description the vegapuls 63 is suitable for connection to the following rtus with modbus rtu or ascii protocol. Rtu protocol abbtotalflow modbus rtu, ascii bristol controlwavemicro modbus rtu, ascii fisher roc mo...
Page 81
81 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 register name register number type configurablevalues default value unit address 200 word 1 … 255 246 – baud rate 201 word 1200, 2400, 4800, 9600, 19200 9600 – parity 202 word 0 = none, 1 = odd, 2 = even 0 – stopbits 203 ...
Page 82
82 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 register name register number type note status 1424 dword see register 100 tv 1426 third variable in byte order cdab status 1436 dword see register 100 qv 1438 quarternary variable in byte order cdab status 2000 dword see...
Page 83
83 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 unit code measurement unit 112 cubic feet 113 cubic inches 11.4 modbus rtu commands fc3 read holding register with this command, any number (1-127) of holding registers can be read out. The start register, from which the ...
Page 84
84 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 request: parameter length code/data function code 1 byte 0x06 start address 2 bytes 0x0000 to 0xffff number of registers 2 bytes data response: parameter length code/data function code 1 byte 0x04 start address 2 bytes 2*...
Page 85
85 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 request: parameter length code/data function code 1 byte 0x10 start address 2 bytes 0x0000 to 0xffff register value 2 bytes 0x0001 to 0x007b byte number 1 byte 2*n register value n*2 bytes data response: parameter length ...
Page 86
86 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 response: parameter length code/data function code 1 byte 0x2b mei type 1 byte 0x0e read device id code 1 byte 0x01 to 0x04 confirmitylevel 1 byte 0x01, 0x02, 0x03, 0x81, 0x82, 0x83 more follows 1 byte 00/ff next object i...
Page 87
87 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 report level (and temperature) request: parameter length code/data report level (and temperature) 4 characters ascii uuu? Response: parameter length code/data report level (and temperature) 24 characters ascii uuudlll.Llf...
Page 88
88 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 response: parameter length code/data assign unit number 6 characters ascii uuunok uu = new address set number of floats request: parameter length code/data set number of floats 5 characters ascii uuufn response: parameter...
Page 89
89 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 response: parameter length code/data set receive to transmit delay 6 characters ascii uuurok report number of floats request: parameter length code/data set receive to transmit delay 4 characters ascii uuuf response: para...
Page 90
90 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 11.6 configurationoftypicalmodbushosts fisher roc 809 wiring plan + + power suppl y modbus d0 d1 is gnd usb b com z y a (rx/tx -) (rx/tx +) 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd fig. 50: connection of veg...
Page 91
91 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 abb total flow wiring plan + + power supply modbus d0 d1 is gnd usb 1 2 13 45 2o ff on ( ) ( ) (-) (-) 8 1 2 6 7 bus + bus - gnd vbat fig. 51: connection of vegapuls 63 to rtu abb total flow 1 vegapuls 63 2 rtu abb total ...
Page 92
92 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 thermo electron autopilot wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 2 1 rx - rx+ fig. 52: connection of vegapuls 63 to rtu thermo electron autopilot 1 veg...
Page 93
93 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 bristol controlwave micro wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 2 3 13 45 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd 1 +sv rs 485 on com1 2 rx- 5 rxt 6 txt 3 tx- 4 gnd 7 not used 8 not used fig. 53: conn...
Page 94
94 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 scadapack wiring plan + + power suppl y modbus d0 d1 is gnd usb 1 3 2 13 45 5 2 1 3 4 9 6 7 8 2o ff on ( ) ( ) (-) (-) +8 +30 vdc to gnd com part 3 (c3) rs485 txd- txd+ gnd fig. 54: connection of vegapuls 63 to rtu scadap...
Page 95
95 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 housing 2 1 ø 79 mm (3.11") ~ 84 mm (3.31") m16x1,5 112 mm (4.41") m20x1,5/ ½ npt ~ 87 mm (3.43") m16x1,5 ø 84 mm (3.31") 120 mm (4.72") m20x1,5/ ½ npt fig. 55: dimensions of housing - with integrated display and adjustme...
Page 96
96 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 vegapuls63,flangeversion,lowtemperature 202 mm (7.95" ) 3 3 ø 44 mm (1.73") 4 mm / 8m m (0.16" / 0.32" ) ø 75 mm (2.95") 15,5 mm (0.61") 202 mm (7.95" ) 31,5 mm (1.24") 1 2 4 mm / 8m m (0.16" / 0.32" ) fig.57:vegapuls63,f...
Page 97
97 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 vegapuls63,hygienicfitting1 ø 90 mm (3.54") ø 78 mm (3.07") 101 mm (3.98") 38 mm (1.50") 15 mm (0.59") 101 mm (3.98") 38 mm (1.50") 15 mm (0.59") 89 mm (3.50") 16 mm (0.63") ø 50 mm (1.97") 15 mm (0.59") 83 mm (3.27") ø 9...
Page 98
98 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 vegapuls63,hygienicfitting2 iso2852 dn 50 / 2" w clamp-stutzen clamp-socket din32676/ dn 50 / 2,5" dn 65 / 3" dn 80 / 3,5" dn 100 / 4" ø 64 ø 77,5 ø 91 ø 106 ø 119 2 3 3 15,4 mm (0.6") w 98 mm (3.86") 161 mm (6.34") 31,5 ...
Page 99
99 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 vegapuls63,hygienicfitting3 1 5 5 2 3 4 5 5 16,5 mm (0.65") ø 92 mm (3.62") ø 124 mm (4.88") 99 mm (3.90") 15,4 mm (0.6") 100 mm (3.94") 163 mm (6.42") 31,5 mm (1.24") 163 mm (6.42") 32,5 mm (1.28") ø 94 mm (3.70") ø 133 ...
Page 100
100 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 vegapuls63,hygienicfitting4 ø 84 mm (3.31") ø 114 mm (4.49") 163 mm (6.42") 31,5 mm (1.24") 100 mm (3.94") 15,4 mm (0.61") 1 2 4 4 100 mm (3.94") 15,4 mm (0.61") 3 ø 65 mm (2.56") ø 105 mm (4.13") 4 fig.61:vegapuls63,hyg...
Page 101
101 11 supplement vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 11.8 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nä...
Page 102: Index
102 index vegapuls 63 • modbus and levelmaster protocol 41364-en-170711 index a adjustment 43, 44 – system 34 b backlight 46 c connection procedure 28 connection technology 28 copy instrument settings 52 current output, min./max. 45 current output mode 44 d damping 44 date/time 50 default values 51 ...
Page 103
103 notes vegapuls 63 • modbus and levelmaster protocol 41364-en-170711.
Page 104
Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 41364-en-17071 1 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subje...