KEB COMBIVERT F6 Instructions For Use Manual - page 22
2.4.1 Voltage outputs of the control terminal block
Name
24Vout
Function
Voltage output (SELV) for input control
Output voltage
minimum P24V_IN - 3 V
maximum P24V_IN
permissible total current
100 mA for all 24Vout outputs together
(short-circuit proof)
Table 7:
Voltage output of the control
2.4.2 Connection and specification of the digital inputs
Name
DI1…DI8
Number
8
Classification
Type 3 in accordance with DIN EN 61131-2
Specification
Status 0
Status 1
U
Low
I
Low
U
High
I
High
max.
5 V
3 mA
1)
30 V
3 mA
1)
min.
-3 V
notdefined
11 V
2 mA
1)
15 mA according to standard
Table 8:
Specifications of the digital inputs
Internal voltage supply
external voltage supply
4
6
8
3
2
1
5
7
26
4
6
8
3
2
1
5
7
9
+
Figure 4:
Connection of the digital inputs at X2A
► Input X2 A.1 can be used as digital or analog input.
► The function is switchable via software.
22
ASSIGNMeNT OF The TeRMINAL STRIP X2A