► Input X2 A.1 can be used as digital or analog input.
► The function is switchable via software.
RESTRICTION
The analog input is not intended for the control with a potentiometer. The analog voltage
must be able to supply the input current.
Input type
non-isolated absolute input
Analog input 3
X2A.1 (AN3+), X2A.9 (0V)
Voltage input DC
0.2…10 V / max. 3 mA
Table 12: Specification of the analog input 3
2.4.6 Specification and connection of the analog output
Analog output
Terminal X2A.22
0V reference voltage for analog output
Terminal X2A.21
DC voltage output
0.1…10 V (
≙ 1…100 % output value)
maximum current
5 mA
Table 13: Specifications of the analog output
21
22
Imax=5mA
U
DC
: 0,1…10V
Figure 8:
Example for the connection of the analog output to X2A
2.4.7 Voltage input for supply of the control board and the brake
The COMBIVERT F6 is supplied via terminals X2B.27 and X2B.28.
27
28
0V
P24V_IN
X2A
PIN
Name
Notes
X2A.27 0V
Reference potential for
P24V_IN
X2A.28 P24V_IN
VoltageinputDC+24V;max.
4.5 A
Tolerance ±5 %
2 A therefrom for the control
of an external brake
Figure 9:
Voltage input of the control
25
ASSIGNMeNT OF The TeRMINAL STRIP X2A