2.7 Fieldbus interfaces
The 9th digit of the material number displays if, in addition to the CAN bus, a real-time
Ethernet bus module (RTE) is installed.
Material number
y
Multifieldbusmodule
xxF6xxx-xyxx
0
without
1
with
Theactivefieldbusinterfaceisdefinedwithfb68.Themeaningofthelightpatternofthe
status LED "NET ST" changes accordingly.
Instructions for use for the real time ethernet moduel:
ma_dr_rte-inst-20148981_en.pdf
2.7.1 CAN
2.7.1.1 ConnectionandspecificationoftheCANbus
X2A.23
X2A.24
X2A.25
CAN_L
CAN_H
CAN_GND
CAN_L
CAN_H
CAN_GND
COMBIVERT
CAN
Node x
CAN
Node x
120Ω
120Ω
Terminal strip X2A
Name
Notes
23
CAN low
no internally bus termination
24
CAN high
25
CAN GND
potential-free CAN ground (can be wired de-
pending on the client)
Figure 12: Connection CAN bus to terminal block X2A
Transmission level
inaccordancewithDINISO11898;ISOHigh
Speed
Transmission speed
20, 25, 50, 100, 125, 250, 500, 1000 kbit/s ad-
justable via (fb66: CAN baud)
Potential separation
No safe isolation between CAN potential and
control potential according to VDE 0160.
Bus termination
124Ωexternalbetween(CAN-HandCAN-L)at
both ends of the bus cable.
Table 17: Specifications of the CAN bus
29
FIeLDbUS INTeRFACeS