KEB COMBIVERT F6 Instructions For Use Manual - page 23
2.4.3 Connection and specification of the digital outputs
Name
DO1…DO2
Number
2
Type
24 V high-side switch
Classification
in accordance with DIN EN 61131-2
Output voltage
minimum P24V_IN - 3 V
maximum P24V_IN
permissible output current
100 mA per output (short-circuit proof)
Others
onlyohmicload;
no internal free-wheeling path
Table 9:
Specifications of the digital outputs
Connection appliance
Connection to an external control
11
12
9
10
11
9
10 12
COM
DI1
DI2
ext.
Figure 5:
Examples for the connection of the digital outputs at X2A
2.4.4 Connection and specification of the relay output
Name
R1
Number
1
maximum DC voltage
30 V
minimum current
0,01 A
maximum current
1 A
maximum number of switching cycles
10
8
mechanically;
500,000 at 1 A and 30 V
Others
onlyohmicload;
no internal free-wheeling path
Table 10: Specifications of the relay output
23
ASSIGNMeNT OF The TeRMINAL STRIP X2A