Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 14
Installation
Sentinel Kinetic MVHR Installation & Commissioning
14
Vertical Discharge Condensate Installation
Note
The 22 mm diameter condensate pipe is suitable for standard 22 mm plastic push-fit fittings and can
be connected vertically underneath the unit or horizontally at the rear.
To install the vertical discharge condensate:
1. For vertical discharge, remove the rear cover and
locate the condensate stub at the rear of the unit.
2. Remove the black Cap from the end of the
condensate stub at the rear of the unit.
3. If not already fitted, fit the flexible condensate pipe
and secure with worm drive clip
The condensate pipe can be attached with a worm
drive clip to a 22 mm vertical pipe.
Fit a ‘U’ bend condensate drain having a minimum
of a 60mm water seal or a HepVo valve to the
building’s foul water drainage system and ensure
there is a minimum 3 degree fall to allow
condensate drainage.
4. Go to Spigot Installation on page 17.