Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 42
Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
42
Table 3: Default Settings
Parameters
Settings
Start-up Screens
Sentinel Kinetic
Sentinel Kinetic
Language
English.
Control Mode
01
Airflow Units
%.
Commissioning Screens
Security PIN
Not set
Boost Supply/Extract
50 %
Normal Supply/ Extract
30 %
Low Supply/Extract
20%
Cooker Hood
supply / extract
30% / 100%
Boost Overrun
15
Boost Delay
00
Boost On/Off
All days set to 0:00 (on), 00:00 (off) – inactive
Normal On Off
All days set to 0:00 (on). 00:00 (off) – inactive
Set Service No
Not set
Humidity
70%
Proportional 1
Humidity – Boost, Normal (60 %)
CO2 – Boost (2000 ppm), Normal (1000 ppm)
Temperature – Boost (27 C, Normal (17 C)
Proportional 2
CO2 – Boost (2000 ppm), Normal (1000 ppm)
Temperature – Boost (27 C, Normal (17 C)
Humidity – Boost, Normal (60 %)
SW4
Off, or with Vent-Wise card fitted 25 mins
Vent-Wise 1/2/3
Load Pot (60 %)
Time Pot (20 m)
Boost Button
On
Summer Bypass
Not Fitted
Antifrost
Airflow Mode
Dryout
Off
Running Time
-
Filter Service
Suburban (default) 12 months, or can be set to Urban and Rural
BMS
On
Restore Defaults
Off
User Screens
Set Clock
-
Summer Bypass
Summer Bypass On
Indoor Temp
25C
Outdoor Temp
14C