Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 33
Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
33
Normal Supply Screen
The Normal Supply screen enables you to set the
Normal airflow speed for the Supply fan in order to
balance out any differences in ductwork or other
installation features.
Default Normal speed = 30%
See graph on either page 10, 11 or 12 for setting the
Supply airflow.
The Normal speed cannot be set below Low speed or
above Boost speed setting.
Normal Supply
30 %
Normal Extract Screen
The Normal Extract screen enables you to set the
Normal airflow speed for the Extract fan in order to
balance out any differences in ductwork or other
installation features.
Default Normal speed = 30%
See graph on either page 10, 11 or 12 for setting the
Extract airflow.
The Normal speed cannot be set below Low speed or
above Boost speed setting.
Normal Extract
30 %
Low Supply Screen
The Low Supply screen enables you to set the Low
airflow speed for the Supply fan in order to balance out
any differences in ductwork or other installation
features.
Default Low speed = 20%
See graph on either page 10, 11 or 12 for setting the
Supply airflow.
The Low speed cannot be set below 1% or above
Normal speed setting.
Low Supply
20 %
Low Extract Screen
The Low Extract screen enables you to set the Low
airflow speed for the Extract fan in order to balance out
any differences in ductwork or other installation
features.
Default Low speed = 20%.
See graph on either page 10, 11 or 12 for setting the
Extract airflow.
The Low speed cannot be set below 1% or above
Normal speed setting.
Low Extract
20 %