Sentinel Kinetic MVHR Installation & Commissioning
52
Remote LED Indicator (448347)
The LED terminals are intended to drive a remote LED to indicate that there is a message in the control display.
They provide a 5 V LED driving signal output between the + and – terminals that enables remote indication of filter
check or unit fault. See the Control Panel for message (See page 45 for fault codes).
Connect the 2 core flying lead from the Remote LED indicator terminal block. Terminal 1 on the Remote LED is +
and terminal 2 is -
Connect the other end of the lead to the LED + &- terminals on the Kinetic unit PCB. Please ensure that the +
goes to + and the – goes to -.