Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 16
Installation
Sentinel Kinetic MVHR Installation & Commissioning
16
4. N.B. SEE “WALL MOUNTING” on page
17 for information on marking out the
wall for the position of the condensate
drain and wall mounting brackets.
Fit Vertical discharge 32mm waste pipe
(fitted with 22 / 32mm reducer ).
Fit a ‘U’ bend condensate drain having a
minimum of a 60mm water seal or a
HepVo valve to the building’s foul water
drainage system and ensure there is a
minimum 3 degree fall to allow
condensate drainage.
5. Fit the flexible condensate pipe to a
22mm diameter x 280mm long
condensate pipe with worm drive clip.
6. Fit pipe assembly into waste pipe and
secure to condensate spigot with worm drive clip.
N.B. Always insulate condensate pipe if installing in a cold void