Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 36
Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
36
Normal On/Off Screen
The Normal Airflow mode can be set to run during the
daytime i.e. from 6am to 11pm, the Low Airflow mode
will then run during the night from 11pm to 6pm.
The Normal On/Off screen enables you to set a time for
Normal to be activated for each day of the week.
You can set up to one On/Off time per day, If On and
Off times are the same, the unit will not change speed.
On time cannot be set earlier than a previous off time,
Likewise, Off time cannot be set earlier than a previous
On time.
To set a weekly schedule:
Setting starts at Mon and uses
to show, by flashing,
which item is available for adjustment with the
and
buttons (a → b → c → d → e → Mon and so on).
Mon 10:01 11:11
↑ ↑ ↑ ↑ ↑
a b c d e
When Day flashes, pressing
(> 2 sec) will copy
yesterday’s times to today.
Setting finishes when the last off minutes for Sun are
accepted, at which point the screen will now show
All Set or holding the
button for 3 seconds.
Normal On Off
Mon 00:00 00:00
Normal On Off
All Set
Set Service No Screen
The Set Service No screen enables you to enter the
telephone number that should be called for service in
the event the unit fault.
Initially the screen is blank. Press
to get a 0. Use
and
buttons to change between 0 and 9 (or
blank). Repeat until the number is entered. Finally,
select a blank and press
to finish. Maximum 16
digits.
Press and hold
for more than 2 seconds to clear
service number.
Set Service No
Internal Humidity Sensor Screen (if fitted)
The Humidity Sensor screen enables you to
switch the Sensor On and adjust the trigger point
between 60% and 90%. (default setting 70%).
Humidity Sensor
Off
(Day)
(Day)
(On)
(On)
Repeat for Off
Repeat for each
Day.
Note: if same
times are used
on subsequent
days,
will
copy times
found.