Vent-Axia Sentinel Kinetic B Left Installation & Commissioning Manual - page 47
Appendix One
Sentinel Kinetic MVHR Installation & Commissioning
47
Appendix One: Control Mode 02 Description
Overview
The functional differences described in this Appendix are available when Control Mode 02 is selected from the
start-up screens. Control Mode 02 assigns alternative functions to certain wiring Terminal Connections and
allows additional airflow settings to be accessed via the
button on the front of the Kinetic unit or remote
control.
N.B.1. If control mode 02 is selected then SW5 must have a link connecting the +
and – terminals or a normally closed device such as a fire system.
N.B.2. Vent-Wise accessories will not function if Control Mode 2 is selected.
Terminal Connections and Functions
The following switching Functions are available with Control Mode 02:
Terminal No.
Name
Description (Control Mode 02)
S/W1
Switch 1
With link fitted to J4 – Volt- free switch – Low Mode
S/W2
Switch 2
With link fitted to J4 – Volt- free switch – Normal Mode
S/W3
Switch 3
With link fitted to J4 – Volt- free switch – Boost Mode
S/W4
Switch 4
Volt-free contact for sensor input between + and – terminals
(Momentary if SW/4 if SW4 Commissioning Screen set On)
S/W5
Switch 5
Fire System or SW/5 open Stop
P1 0-10V
Proportional 1
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
P2 0-10V
Proportional 2
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
LED
Red Light Emitting Diode
Output
A 5 V LED driving signal output between the + and – terminals that
enables remote indication of a unit fault. See the Control Panel for fault
code (see Service/Fault Code Screens on page 45).
L
Mains Live
220-240 V AC, 50 Hz input
N
Mains Neutral
220-240 V AC, 50 Hz input
EARTH
Mains Earth
Earthing connector
LS
Switched Live
220-240 V AC, 50 Hz input