Samlexpower Evolution EVO-2212 Owner's Manual - page 113
20 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 21
APPENDIX A
SECTION 4 |
Parameter Setup
ates in “Charging Mode” and qualified AC input from the Grid / Generator is passed through
to the AC Output and at the same time, the Internal AC Charger starts charging the battery.
If an external charger is also connected to the External Charging Terminals, the internal AC
Charger will limit the charging current to a value = (Programmed Value of Charging Current –
Value of Current fed from the External Charger). When the Grid / Generator AC input fails or is
not within the programmed value of voltage and frequency, the Transfer Relay is de-energized,
the unit changes over to “Inverting Mode” and the AC Output is fed from the internal Inverter
Section. When Grid / Generator input is restored, the unit reverts back to “Charging Mode”.
On-line Mode is programmed through the Remote Control EVO-RC by setting ONLINE MODE
[1=ON] as shown in the steps given below. The Default Setting is Off-Line Mode [0=OFF].
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
ONLINE MODE
0=Off
Enter Key
ò
Up Key x 12
ò
RECONNECT VOLT:
As explained under "ON-LINE MODE" above, "RECONNECT VOLT" setting is the battery
voltage at which the unit transfers from "Charging Mode" to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
RECONNECT
14.00V
Enter Key
ò
Up Key x 13
ò
4.5 GROUP 2 PARAMETER SET UP: INPUT SETTING
Please refer to Parameters under Group 2 at Fig 4.1. Details of Parameter set up are given below:
TABLE 4.5. GROUP 2 PARAMETER SET UP: INPUT SETTING
Page
No. for
Group
2 (Fig
4.1)
Parameter
Setting range
Default value
2212
3012
2224
4024
2212
3012
2224
4024
1
DEFAULT FREQ
50 / 60Hz
60Hz
2
MAXIMUM CURRENT 5 – 40A 5 – 70A 5 – 40A
5 – 70A
30A
3
HIGH CUT OFF
50 – 70Hz
65Hz
4
HIGH RESET
50 – 70Hz
64Hz
5
LOW CUT OFF
40 – 60Hz
55Hz
6
LOW RESET
40 – 60Hz
56Hz
DEFAULT FREQ:
Default frequency sets the Inverter frequency, which is also the standard frequency for AC input.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
DEFAUT FREQ
0= 60Hz
Up Key
ò
Enter Key
ò
MAXIMUM CURRENT:
In Charging Mode, the net AC input current from the Grid/Generator is the sum of the AC