explosive gas mixture. Care should be taken to ventilate the battery area and follow
the battery manufacturer’s recommendations.
•
Never smoke or allow a spark or flame near the batteries.
•
Use caution to reduce the risk of dropping a metal tool on the battery. It could spark
or short circuit the battery or other electrical parts and could cause an explosion.
Always use insulated tools.
•
Remove metal items like rings, bracelets and watches when working with batteries.
Batteries can produce a short circuit current high enough to weld a ring or the like to
metal and thus cause a severe burn.
•
If you need to remove a battery, always remove the Ground terminal from the battery
first. Make sure that all the accessories are off so that you do not cause a spark.
TABLE 1.1 (a) SIZING OF AC INPUT WIRING AND BREAKERS
(FOR DEFAULT AC INPUT CURRENT LIMIT PROGRAMMED AT 30A
FOR EVO=2212, EVO-2224, EVO-3012, EVO-4024)
Item
(Column 1)
Programmed
Input Cur-
rent Limit
(Column 2)
NEC Ampac-
ity = 125% of
Column 2
(Column 3)
Size based on NEC Am-
pacity at Column 3 and
75°C Copper Conductor
in Conduit
(Column 4)
Breaker Size
(Based on NEC Am-
pacity at Column 3)
(Column 5)
EVO-2212
30A
(Default)
37.5A
AWG #8
40A
EVO-2224
EVO-3012
EVO-4024
TABLE 1.1 (b) AC INPUT WIRING AND BREAKERS
(FOR AC INPUT CURRENT LIMIT PROGRAMMED AT 45A FOR EVO-3012 AND EVO-4024)
Item
(Column 1)
Programmed
Input Cur-
rent Limit
(Column 2)
NEC Ampac-
ity = 125% of
Column 2
(Column 3)
Wire Size based on
NEC Ampacity at
Column 3 and 75°C
Copper Conductor in
Conduit
(Column 4)
Breaker Size
(Based on NEC Am-
pacity at Column 3)
(Column 5)
EVO-3012
45A
56.25A
AWG #6
60A
EVO-4024
TABLE 1.1 (c) AC INPUT WIRING AND BREAKERS
(FOR AC INPUT CURRENT LIMIT PROGRAMMED AT 60A FOR EVO-4024)
Item
(Column 1)
Pro-
grammed
Input Cur-
rent Limit
(Column 2)
NEC Ampac-
ity = 125% of
Column 2
(Column 3)
Wire Size based on
NEC Ampacity at
Column 3 and 75°C
Copper Conductor in
Conduit
(Column 4)
Breaker Size
(Based on NEC Am-
pacity at Column 3)
(Column 5)
EVO-4024
60A
75A
AWG #4 or
2 X AWG #6
80A
SECTION 1 |
Safety Instructions & General Information