46 | SAMLEX AMERICA INC.
capacity of the specific model when operating in Inverter Mode (Column 1 ).
•When Grid / Generator input is available and the unit is operating in Charging / Pass
Through Mode, the AC Input Current will be determined as follows:
•The maximum possible AC Input Current (Column 4) for a particular model will be
equal to the sum of the Rated AC Side Battery Charging Current (Column 3) and the
Rated Pass Through current (Column 2). Rated Pass Through Current (Column 2) = the
Rated Output Current in Inverter Mode (Column 1).
• The AC Input current in Charging / Pass Through Mode will be restricted by the
maximum Amp rating of the Generator or the Amp rating of the breaker in the Grid
Branch Circuit that is feeding the unit. The AC Input Current drawn by the unit can be
programmed to the desired limit (Column 5) to match the output Amp rating of the
Generator or the Amp rating of breaker in the Grid Branch Circuit. Optional Remote
Control EVO-RC is required to change this limit (See Appendix A under Group 2 Pa-
rameter Select for Input Settings-"Max Current"). All the 4 models EVO-2212, 2224,
3012 and 4024 come with Input Current Limit set at 30A (Default Setting). See Table
3.2.1.
•Higher Power Models will require higher Amp rating of the Generator / the Grid
Branch Circuit. Wiring and breaker sizing for Input Current Limit at 45A for EVO-
3012, 4024 is given at Table 3.2.2 and for 60A for EVO-4024 is given at Table 3.2.3.
TABLE 3.2.1 SIZING OF GRID AND GENERATOR INPUT WIRING AND BREAKERS (FOR DEFAULT INPUT
CURRENT LIMIT PROGRAMMED AT 30A FOR EVO-2212, EVO-2224, EVO-3012, EVO-4024)
Model No. and
Rated Output
Power in In-
verter Mode
(Column 1)
Rated
AC Pass
Through
Current
(See Note
1)
(Column 2)
Rated AC
Charging
Current
(See Note
2)
(Column 3)
Total Rated
AC Input
Current
(Columns
2 +3)
(See Note 3)
(Column 4)
Pro-
grammed
AC Input
Current
Limit
(See Note
4)
(Column 5)
NEC Ampac-
ity = 125% of
Column 5
(See Note 5)
(Column 6)
Conductor
Size Based
on NEC
Ampacity at
Column 6
(See Note 6)
(Column 7)
External
Breaker
Size
Based
on NEC
Ampacity at
Column 6
(See Note 7)
(Column 8)
EVO-2212
(2200VA, 18A)
18 A
15A
33A
30A
(Default)
37.5A
AWG #8
40A
EVO-2224
(2200VA, 18A)
18A
19A
37A
EVO-3012
(3000VA, 25A)
25A
20A
45A
EVO-4024
(4000VA, 33A)
33A
29A
62A
SECTION 3 |