TABLE 6.6 PROGRAMMABLE AND DEFAULT PARAMETERS - GROUP "OTHER FUNCTIONS"
Parameter name
Setting range
Default Value
2212
3012
2224
4024
2212
3012
2224
4024
“POWER SAVING”
1 = Enable 0 = Disable
Enable
• “ENTER POINT”
4 – 50W
6W
8W
6W
8W
• “WAKE UP POINT”
5 – 50W
7W
10W
7W
10W
“REMOTE SWITCH”
• For ON /OFF control
through external 12V
signal fed to Remote
ON / OFF terminals on
the Front Panel (15,
Fig 2.1)
0 = Button Type: 12V signal is fed
through Push Button Type of Switch
• Pressing of Push Button > 2 sec
will switch the unit ON
• When ON, pressing Push Button
> 5 sec will turn the unit OFF
1 = Switch Type: 12V signal is fed
through contacts of Toggle Type of
Switch or relay contact
• ON condition (contacts closed)
will turn the unit ON
• OFF condition (contacts open)
for 2 sec will switch the unit OFF
0 = Button Type
CAUTION! ON/OFF Logic also controls the
operation of the ON/OFF Button on the
front panel (11, Fig 2.1). The Default setting
is "Button Type".
If the ON/OFF Control is changed to external
"Remote Switch", it will not be possible to
switch ON/OFF the EVO Inverter Charger
from the front panel ON/OFF Push Button
because it will work with Switch Type
Logic. It will be ON only as long as the Push
Buttom is kept pressed and will switch OFF
when released.
“RELAY FUNCTION”
0 - Relay will be ON (contacts will
close) when in “Charging Mode”
1 - Relay will be ON (contacts will be
closed) in Fault Mode
2 - Used for Generator Auto Start /
Stop with the help of optional
Generator Auto Start / Stop
Module.
• Relay will be ON (contacts will
close) at Low Battery Alarm
• Relay will be OFF (contacts will
open) at Low Battery Reset.
2 = Generator
“COMM ID”
(Communication ID for
optional Remote Control
EVO-RC)
1 - 255
1
“BUZZER”
0 = OFF ; 1 = ON
1 = On
“DISCHARGE BEEP”
(Beeping in “Discharg-
ing / Inverter Mode”)
0 = OFF ; 1 = ON
0 = Off
“DEFAULT RESET”
0 = No ; 1 = YES
0 = No
DATA LOG TIME
(For Optional Remote
Control EVO-RC)
0 = Disable 3 = 30 sec 6 = 10 min
1 = 1 sec 4 = 60 sec
1
2 = 10 sec 5 = 5 min
1
1 = 1 sec
PARAMETER SAVE
(For Optional Remote
Control EVO-RC)
0 = No
1 = Yes
0 = No