Samlexpower Evolution EVO-2212 Owner's Manual - page 118
26 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
4.8 GROUP 5 PARAMETER SET UP: OTHER FUNCTIONS
Please refer to Parameters under Group 5 at Fig 4.2. Details of Parameter set up are given below:
TABLE 4.8. GROUP 5 PARAMETER SET UP: OTHER FUNCTIONS
Page
No. for
Group 5
(Fig 4.2)
Parameter
Setting range
Default value
2212
3012
2224
4024
2212
3012
2224
4024
1
POWER SAVING
1 = Enable 0 = Disable
1 = Enable
2
ENTER POINT
4 – 50W
6W
8W
6W
8W
3
WAKE UP POINT
5 – 50W
7W
10W
7W
10W
4
REMOTE SWITCH
0 = Button Type
1 = Switch Type
Button type
5
RELAY FUNCTION
0 = Charge/Other
1 = Normal/Fault
2 = Generator
2 = Generator
6
COMM ID
1 – 255
1
7
BUZZER
1 = ON
0 = OFF
1 = ON
8
DISCHARGE BEEP
1 = ON
0 = OFF
0 = OFF
9
DEFAULT RESET
0 = No
1 = Yes
0 = No
10
DATALOG DISABLE
DATALOG TIME
0 = Disable, 1 = 1 sec, 3 = 30 sec
4 = 1 min, 5 = 5 min, 6 = 10 min
1 = 1 sec
11
PARAMETER SAVE
0 = No
1 = Yes
0 = No
POWER SAVING:
Enable or disable Power Saving Mode when in "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
ENTER POINT:
If the value of power drawn by AC load falls to the "ENTER POINT" value for 5 sec, the unit
will enter "Power Save Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
ENTER POINT
6W / 8W
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 1
ò