• When in Charging Mode, the Neutral conductor of the Grid power/Generator will be
connected to the Output Neutral connector of the Inverter Charger. At the same time, the
“Output Neutral to Chassis Ground Bond Switching Relay” [K4 in Figs 4.1(a) and 4.1(b)] will
unbond (disconnect) the Output Neutral connector of the Inverter Charger from the chassis
of the Inverter Charger. This will ensure that the Grounded Conductor (GC) / Neutral of the
Grid power/Generator is bonded to the Earth Ground at one single point at the location of
the AC Power Distribution System of the Marina/RV Park.
• Disabling Neutral to Ground Bond: In some applications, the Output Neutral may be
required to remain isolated from the chassis/Ground at all times. For this, automatic Ouput
Neutral to Chassis Ground bond can be disabled by disconnecting the Male/Female Quick
Disconnect located in the AC wiring compartment. [Please see (i) 13, Fig 3.9 and (ii) "QD" in
Figs 4.1(a) and 4.1(b)].
Please read the following on-line White Papers for more details at www.samlexameri-
ca.com (Home > Support > White Papers):
- “Neutral to Ground Switching in RV and Marine Applications”